TW Series / Water to Water
reset to DE. The ND setting could be selected at
start-up to avoid prolonged waiting periods during
commissioning.
Once selected hit the “mode” key to advance.
Setting:______________________
Sixth display eld
Compressor setting, (Si) single or (Du) dual. Use
the up or down arrows to select. Hit the “mode” key
to advance. This is only applicable on multi stage
units. If set to Si on a dual circuit unit the second
stage will not come on. Must be set to “DU” for al
TW models.
Setting:______________________
Seventh display eld
Lead\lag setting (dual compressor only). Set point
is 0 to 14 days on lead compressor rotation se-
quence. Use up or down arrows to select. Hit
“mode” key to advance. Must be set to “0” for all
TW models.
Setting:______________________
Eighth display eld
Malfunction output setting, (Pu) pulsed or (St)
standard constant on. This sets the malfunction
output relay to mimic the fault blink code that is
causing the safety lock-out. This can be used for
remote monitoring and remote trouble shooting.
Use the up or down arrows to select. Hit the
“mode” key to advance.
Setting:______________________
The controller is now congured and is fully
operational.
A copy of this conguration sheet should be left
with the home owner or building manager for their
records of initial control settings.
SYSTEM CHECKOUT
After completing the installation, and before
energizing the unit, the following system checks
should be made:
Verify that the supply voltage to the unit is in
accordance with the nameplate ratings.
Make sure that all electrical connections are tight
and secure.
Check that the eld wiring and the electrical
fusing are the correct size.
Verify that the low voltage wiring between the
primary controller and the unit is correct.
Verify that the water piping is complete and
correct.
Check that the water ow is correct, adjust if
necessary.
Verify that vibration isolation has been provided.
Be certain that the unit is serviceable, and all
access panels are secured in place.
UNIT START-UP
1. Set the primary controller to the highest set-
ting.
2. Set the primary controller system switch to
“COOL. The reversing valve solenoid should
energize. The compressor should not run.
3.
Reduce the primary controller setting approxi-
mately 5 degrees below return uid temperature.
4. Verify the heat pump is operating in the cooling
mode.
5. Check the cooling refrigerant pressures against
the values listed in Table #1.
6. Turn the primary controller system switch to the
“OFF” position. The unit should stop running
and the reversing valve should de-energize.
7. Leave the unit off for approximately (5) minutes
to allow for system equalization.
8. Turn the primary controller to the lowest setting.
9. Set the primary controller switch to “HEAT”.
10. Increase the primary controller setting
approximately 5 degrees above the return uid
temperature.
11. Verify the heat pump is operating in the heating
mode.
12. Check the heating refrigerant pressures against
the values listed in Table #2.
13. Set the primary controller to maintain the
desired return uid temperature.
14. Check for vibrations, leaks, etc...
15. Instruct the owner on the unit and control
operation.
System Checkout