6 720 220 047
Revised 03-11 Subject to change without prior notice
9
TW Series / Water to Water
compressor in a two stage unit). When the set point
is satised the compressor is turned off.
In a two stage unit after the rst stage activation if
the water temperature drops an additional two
degrees below the set point, the second stage
(terminal Y2) will be activated (if control is
congured for both compressors). Both stages will
be on until the set point is satised.
When the unit runs after power is applied or the
mode is changed from cooling to heating, if the
uid temperature is below set point and doesn’t
change for 3 minutes, the second stage of heating
will be activated. This only applies for a two stage
machine.
There will be 5 minutes delay on break after the unit
cycles off on temperature, a power interruption or
because of a fault condition.
At any point in time the control will ignore a low
pressure switch condition for 120 seconds before
turning off the compressor.
COOLING MODE
When the unit is operated in the cooling mode and
the leaving water temperature is above the
temperature set point plus the differential setting,
terminals Y1 will close (rst stage compressor of a
two stage unit) and the unit will operate in the
cooling mode. When the set point is satised the
compressor is turned off. The reversing valve is
always activated when the unit is in the cooling
mode.
On two stage units, after rst stage activation if
water temperature increases two degrees above
the set point, the second stage (terminal Y2) will be
activated (if control is congured for both
compressors). Both stages will remain on until the
set point is satised.
When the unit runs after power is applied or the
mode is changed from heating to cooling, if the
uid temperature is above cooling point and
doesn’t change for 3 minutes, the second stage of
cooling will be activated. This only applies for a two
stage machine.
There will be 5 minutes delay on break after the unit
cycles off on temperature, a power interruption or
because of a fault condition.
AUTO CHANGEOVER MODE
The controller’s auto changeover mode control
feature will switch from the heating mode to
cooling mode and vice versa based on the setting of
the change over sensor. There will be a dead-band
where the control will not call for either heat or
cool. The dead-band setting is adjustable in the
conguration mode. When the auto changeover
mode is selected the changeover set point will be
displayed for 5 seconds however this set point is
only adjustable when the controller is in the
conguration mode. Once the controller has
switched to either the heating or cooling mode,
pressing the Up or Down buttons will display the
set point for that particular mode.
When the reading from the changeover sensor is
above the changeover set point plus the dead-band
setting, the unit will operate in the cooling mode
and will maintain the cooling set point temperature.
While in the cooling mode the user can adjust the
cooling set point. Likewise when the changeover
sensor is below the changeover set point minus the
dead-band setting, the unit will switch to the
heating mode and will maintain the heating set
point temperature. While in the heating mode the
user can adjust the heating set point.
Once the reading from the sensor enters the
dead-band zone it will terminate the call for cooling
or heating even if the set points are not satised.
Mode switching will be HEAT – COOL – OFF in a
closed loop. If the changeover sensor is shorted
when the control is in Auto changeover mode then
the control will switch to the OFF mode. If no
sensor is connected the controller will indicate a
sensor error code.
UNIT PROTECTION
The unit controller will protect the unit against a
high or low pressure condition and brownout. To
avoid nuisance lockouts an intelligent reset
function is built into the controller to allow the unit
to restart one time in the event of a fault condition.
If a fault condition is initiated on any circuit the
corresponding compressor will be turned off and
the 5 minute delay on break time period timer is
initiated. After the delay expires the unit will
attempt to restart. If the fault condition still exists
Cooling Mode
Comments to this Manuals