TW Series / Water to Water
water side pressure drop. See specication sheets
for water ow and pressure drop information.
WELL WATER SYSTEMS (Figure #2)
Water quantity should be plentiful, between 1.5
and 3.0 gpm per ton of cooling, and of good quality.
To avoid the possibility of freezing in the heating
mode, the well water should be above 50˚F.
Water pressure must always be maintained in the
heat exchanger by placing a water control valve on
the outlet of the water-to-water unit. A bladder type
expansion tank may be used to maintain pressure
on the system. All solenoid valves should be slow
closing to avoid water hammer.
The discharge water from the water-to-water unit is
not contaminated in any manner and can be
disposed of in various ways depending on the local
codes (i.e. discharge well, dry well, storm sewer,
drain eld, stream, pond, etc.) Pilot operated or
slow closing valves are recommended to reduce
water hammering.
EARTH COUPLED GEOTHERMAL
SYSTEMS (Figure #3)
Closed loop and pond applications require
specialized design knowledge. No attempt at these
installations should be made unless the dealer has
received specialized training.
Utilizing the Ground Loop Pumping Package
(GLP), makes the installation easy. Anti-freeze
solutions are utilized when entering loop
temperatures drop below 50˚F or where piping
will be routed through areas subject to freezing. A
ow rate between 2.5 to 3.0 gpm per nominal ton
of cooling is recommended for this application.
See GLP Pump Curve for sizing information.
TYPICAL LOAD SIDE APPLICATIONS
There are many load side applications for which
the water-to-water heat pump/ liquid chiller is
ideally suited.
SOME TYPICAL USES ARE AS
FOLLOWS
Hydronic baseboard heating, hydronic in-slab oor
heating, forced air fan coil heating or cooling, ice
and snow melting, heating potable water, (when
allowed by code) heating swimming pool and spa*,
process uid heating or cooling.
When specifying load side uid volume it is
important to consider the heat pump output
capacities and ow rates. Insufcient load side
uid volume may cause unstable heat pump
operation (short cycling). Pressure/temperature
ports should be used to set ow rates.
Well Water Systems
EARTH COUPLED APPLICATION (SOURCE SIDE)
1. POLYBUTYLENE OR POLYETHELENE WITH
INSULATION
2. GROUND LOOP PUMPING PACKAGE (GLP)
3. GROUND LOOP CONNECTION KIT
4. P/T PLUGS
5. LOAD SIDE CONNECTIONS*
6. LOW VOLTAGE CONTROL CONNECTION*
7. VIBRATION PAD
8. LINE VOLTAGE DISCONNECT
Figure #3
* NOTE: Water and electrical connection locations vary depending
on model. Connect as required per unit labels.