Bosch TW Series Specifications Page 5

  • Download
  • Add to my manuals
  • Print
  • Page
    / 24
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 4
6 720 220 047
Revised 03-11 Subject to change without prior notice
5
TW Series / Water to Water
where water released during start-up or
maintenance could cause damage below the unit.
MINIMAL SYSTEM VOLUME
Bosch recommends that the total uid volume in the
system be not less than 6 gallons per nominal ton of
cooling capacity on both the load and source sides.
ELECTRICAL
Caution
Always disconnect power to the unit before
servicing to prevent injury or death due to
electrical shock.
All eld wiring must comply with local and national
re, safety and electrical codes. Power to the unit
must be within the operating voltage range
indicated on the unit’s nameplate. On three phase
units, phases must be balanced within 2%.
Properly sized fuse or HACR circuit breakers must
be installed for branch circuit protection. See
equipment rating plate for maximum size. The unit
is supplied with an opening for attaching conduit.
Be certain to connect the ground lead to the
ground lug in the control box. Connect the power
leads as indicated on the unit wiring diagram
(Refer to Figure #6).
PIPING
Supply and return piping must be as large as the
unit connections on the heat pump (larger on long
runs). Never use exible hoses of a smaller inside
diameter than that of the water connections on
the unit. The Water-to-Water series units are
supplied with either a copper or optional cupro-
nickel condenser. Should your well driller express
concern regarding the quality of the well water
available or should any known hazards exist in
your area, we recommend proper testing to assure
the well water quality is suitable for use with
water source equipment. In conditions
anticipating moderate scale formation or in
brackish water a cupro-nickel heat exchanger is
recommended.
Galvanized pipe or ttings are not recommended
for use with these units due to the possible
galvanic corrosion.
Both the supply and discharge water lines will
sweat if subject to low water temperature. These
lines should be insulated to prevent damage from
condensation.
All manual ow valves used in the system must be
ball valves. Globe and gate valves must not be
Minimal System Volume
COOLING TOWER/BOILER APPLICATION
(SOURCE SIDE)
1. BALL VALVES
2. HOSE KITS
3. P/T PLUGS
4. LOAD SIDE CONNECTIONS*
5. LOW VOLTAGE CONTROL CONNECTION*
6. VIBRATION PAD
7. LINE VOLTAGE DISCONNECT
8. SUPPLY AND RETURN LINES OF
CENTRAL SYSTEM
Figure #1
* NOTE: Water and electrical connection locations vary depending on model. Connect as required per unit labels.
Page view 4
1 2 3 4 5 6 7 8 9 10 ... 23 24

Comments to this Manuals

No comments