Bosch D7412G User Manual Page 108

  • Download
  • Add to my manuals
  • Print
  • Page
    / 142
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 107
D9412G/D7412G | Program Entry Guide | 5.0 RADXSKED EN | 108
Bosch Security Systems | 1/04 | 47775E
S## Cmd Center
Default: Blank (0)
Selections: Blank (0), 1 to 8
Blank (0)
No command center
is specified for
Custom Function
activation.
Identify the specific keypad
(CC #) where the Custom
Function is entered. Only one
command center can be
assigned for this sked function.
1 to 8
Command center
address specified for
Custom Function
activation.
S## Custom Func
Default: Blank (0)
Blank (0)
No Custom
Function is
activated.
11 Execute Custom Func: This function
emulates any of the custom functions
assigned to the command center that
can be executed by a user from the
command center. When a sked executes
a custom function, it is subject to the
scope of the selected command center.
Cmd Center
and
Custom Func
prompts appear after entering Function
Code 11. Both entries are required.
Selections: Blank (0),
128 to 143 for D9412G,
128 to 131 for D7412G
Enter the custom function this
sked executes.
128 to
143
Custom Function to
activate.
Avoid having multiple functions occur at the same time at the same address. Functions can clash and the
effect on the control panel is unpredictable.
0101
0101
0101
Review to make sure that the Custom Function being executed or any of the commands nested inside the
Custom Function are not passcode protected.
0101
0101
0101
Do not program multiple skeds to execute at the same command center during the same time of execution.
Do not program skeds to execute at times when a user is likely to be executing functions at the command
center. If it is necessary to do so, there are two ways to work around the situation:
1. Program CC at the beginning of the Custom Function Key Strokes entry. This aborts the user’s
function and allow the sked to execute.
2. Program the sked to execute at an address (Cmd Center) with no command center physically
attached to it. The CC # must be assigned to an area and have the appropriate scope programmed.
13 Adjust Time Forward One Hour: This sked function is used to make adjustments to the control panel’s
clock. A typical application is to program this to go into effect at 2:00 AM on the date that Daylight Savings
Time begins (during the springtime). No Time Change Report is sent or logged, but the new time appears in
the next report logged.
There are no other parameters that require input for this option.
14 Adjust Time Backward One Hour: This sked function is used to make adjustments to the control panel’s
clock. A typical application is to program this to go into effect at 2:00 AM on the date that Daylight Savings
Time ends (during the fall). This function can operate only once in a day, even if multiple Skeds with this
function are programmed. No Time Change Report is sent or logged, but the new time appears in the next
report logged.
There are no other parameters that require input for this option.
Page view 107
1 2 ... 103 104 105 106 107 108 109 110 111 112 113 ... 141 142

Comments to this Manuals

No comments