D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 20
Bosch Security Systems | 1/04 | 47775E
Test Reports
0101
0101
0101
To send a single Test Report (R# Test
Report), enable Sked Function Code #9
(Test Report) in the Skeds section of the
program.
To expand this Test Report to include any
off-normal point condition or other off-
normal conditions of events listed in Diag
Reports as a Non-status Event following a
Test Report, Expand Test Rpt in Section
2.2 Phone Parameters must be
programmed Yes.
Events R# Log Threshold, R# Log
Overflow, and R# RAM Fail are added to
the reports sent with Expanded Test
Reports if they are enabled in RAM Reports
and Expand Test Rpt is also enabled.
To initiate a Status Report, which includes
all R# S: ____ Events as a Status Event (as
opposed to a Non-status Event), Sked
Function Code #10 must be enabled in the
Skeds section of the program.
Reporting off-normal conditions as a Status
Report following a Test Report is required
by some automation systems. Reporting off-
normal conditions as a Non-status Report,
which follows a Test Report, is required for
other automation systems.
An off-normal condition is any point which is
missing, trouble, supervisory, or in alarm (as
opposed to normal). Also, points not
cleared at the command center report as
off-normal.
Control Panels with Firmware version 6.30
or higher can generate an Expanded Off-
Normal Test Report by using Sked Function
Code 28 or a Non-Expanded Off-Normal
Test Report using Sked Function Code 29.
To generate this event, one or more points
must be in an off-normal state at the time
the Sked executes. Expanded Off-Normal
Test Reports include the Off Normal Test
Report Event as well as events for any
points that are in an off-normal state at the
time the report is generated. Non-Expanded
Off-Normal Test Report Events are only
sent when a point is in the off-normal state
but only sends the Off Normal Test Report
Event.
Table 12: Test Reports
Report Selections Description
R# S: Alarm
Yes, No
Status Alarm Report
R# S: Trouble
Yes, No
Status Trouble
Report
R# S:
Supervised
Yes, No
Status Supervised
Report
R# Status
Report
Yes, No
Status Report
R# S: Open
Yes, No
Status Open Report
R# S: Close
Yes, No
Status Close Report
R# Test Report
Yes, No
Test Report
R# S: Perim
Inst
Yes, No
Status Perimeter
Instant Arm Report
R# S: Perim
Delay
Yes, No
Status Perimeter
Delay Arm Report
R# S: Fire Supv
Yes, No
Status Fire
Supervision Report
R# S: Fire
Alarm
Yes, No
Status Fire Alarm
Report
R# S: Fire Trbl
Yes, No
Status Fire Trouble
Report
R# S: Msng
Fire
Yes, No
Status Fire Missing
Report
R# S:
MsngBurgTr
Yes, No
Status Burg Missing
Trouble Report
R# S:
MsngBurgAl
Yes, No
Status Burg Missing
Alarm Report
R# S:
FireSpMsng
Yes, No
Status Fire
Supervision Missing
Report
R# S:
SuperMsng
Yes, No
Status Non-fire
Supervision Missing
Report
R# S:
DrLeftOpen
Yes, No
Status Door Left
Open Report
Diag Reports
Selecting Yes enables sending a report when the
event occurs. If the off-normal state of the following
events (indicated with an *) still exist, they report
when a Test Report (see the
Test Reports
sub-
prompt in Section 2.3.8 Dialing Attempts) is initiated
and Expanded Test Rpt is programmed Yes.