Bosch D7412G User Manual Page 135

  • Download
  • Add to my manuals
  • Print
  • Page
    / 142
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 134
D9412G/D7412G | Program Entry Guide | 7.0 RADXAXS EN | 135
Bosch Security Systems | 1/04 | 47775E
D# Access Granted?
Default: No
Selection: Yes or No
Yes Access Events from this door controller
are sent to the control panel for
processing.
No
Access Events from this door controller
are not sent to the control panel for
processing.
This program item determines if Access Granted
and Door Request Events are sent to the control
panel for processing memory, printing, and remote
reporting.
0101
0101
0101
A successful Access Event can be
initiated by a(n):
Valid user ID
Valid door state changed at the
command center.
Automatically scheduled or armed
state change that holds a door open
RTE/exit (RTE/REX).
D# No Entry?
Default: No
Selection: Yes or No
Yes
Access Denied Events from this door
controller are sent to the control panel
for processing.
No
Access Denied Events from this door
controller are not sent to the control
panel for processing.
This program item determines if No Entry Events
are sent to the control panel for processing memory,
printing, and remote reporting.
0101
0101
0101
A No Entry Event can be caused by:
Invalid or unknown user ID, interlock or
secured door, or incorrect authority
level
RTE/REX for door in interlock or
secured door.
D# Enter Request?
Default: No
Selection: Yes or No
Yes A Door RTE Event from this door
controller is sent to the control panel
for processing.
No A Door RTE Event from this door
controller is not sent to the control
panel for processing.
This program item determines if RTE Events are
sent to the control panel for processing memory,
printing, and remote reporting.
0101
0101
0101
RTE Events require D# Access Granted
to be programmed Yes.
D# Exit Request?
Default: No
Selection: Yes or No
Yes A Door RTE Event from this door
controller is sent to the control panel
for processing.
No
A Door RTE Event from this door
controller is not sent to the control
panel for processing.
This program item determines if REX Events are
sent to the control panel for processing memory,
printing, and remote reporting.
0101
0101
0101
REX Events require D# Access Granted
to be programmed Yes.
Page view 134