D9412GV2/D7412GV2 | Operation and Installation Guide | 9.0 Off-Board Points
34 Bosch Security Systems, Inc. | 5/05 | F01U003641B
9.0 Off-Board Points
9.1 Point (Zonex) Bus: D9412GV2 Terminals and D7412GV2 Terminals
9.1.1 POPIT Modules
The D9412GV2 can use point of protection input transponder (POPIT) modules to provide a maximum of 238
off-board points, bringing the total number of points the D9412GV2 can monitor to 246. The D7412GV2
provides up to 67 off-board points, bringing the total number of points the D7412GV2 monitors to 75. Each off-
board point requires a POPIT Module.
9.1.2 POPEX Modules
POPITs connect to supervised two-wire data expansion loops run from POPIT to POPIT throughout the
premises. Data expansion loops connect to a D8125 Point of Protection Expander (POPEX) Module. POPEX
Modules have power and data connections to the point bus on the control panel (Table 11).
Table 11: POPEX Modules
Model Power Data
D9412G Terminals 23 and 24 Terminals 25 and 26
or
Terminals 27 and 28
D7412G Terminals 3 and 9 Terminals 22 and 28
9.1.3 Missing Conditions
If a programmed POPIT is disconnected from the expansion loop, a missing condition appears immediately and
the event is logged. The missing condition might also be sent to a central station or printed to an on-site printer, if
programmed to do so. Refer to the D9412GV2/D7412GV2 Program Entry Guide (P/N: F01U003636) for
programming options.
9.1.4 Extra Point Events
Extra Point events are generated when a POPIT connected to the data expansion bus does not have an assigned
Point Index. Table 12 shows when an Extra Point event is or is not generated. Table 13 on page 35 shows
additional error conditions that can occur for the off-board points.
Table 12: Extra Point Events
A POPIT connected to the data
expansion bus does not have an
assigned Point Index and: Extra Point event? Additional Information
Data expansion bus is disconnected No Keypad does not annunciate or display a trouble condition.
Data expansion bus restores to normal
condition after an open condition
Yes
Keypad annunciates and displays a trouble condition
Extra Point is logged and might be programmed to
send reports to the central station or to an on-site
printer.
Point input changes status from normal
to open or shorted
No Keypad does not annunciate or display a trouble condition.
During a Service Walk Test, the point
input changes status from normal to
open or shorted
Yes
Keypad annunciates and displays a trouble condition
Extra Point is logged and might be programmed to
send reports to the central station or to an on-site
printer.
The Service Walk Test never shows the electrical state of a point as “Extra.”