D9412GV2/D7412GV2 | Operation and Installation Guide | 9.0 Off-Board Points
40 Bosch Security Systems, Inc. | 5/05 | F01U003641B
Figure 14: Program Record Sheet
EN | 25
bold
Point Assignments (001 through 040)
POPIT Switch
Setting
Trans-
lation
Point
#
Point
Index
Area
Assign
Debounce
BFSK/
Relay
Custom Point Text
100 001 (3) _ _ (1) ___ (2) _____ (1) ____
P1 FIRE
___________________
200 002 (1) _ _ (1) ___ (2) _____ (2) ____ P2 PANIC ___________________
300 003 (25) _ _ (1) ___ (2) _____ (3) ____ P3 DELAY ___________________
400 004 (13) _ _ (1) ___ (2) _____ (4) ____ P4 FOLLOW ___________________
500 005 (7) _ _ (1) ___ (2) _____ (5) ____ P5 INSTANT ___________________
600 006 (7) _ _ (1) ___ (2) _____ (6) ____ P6 INSTANT ___________________
700 007 (7) _ _ (1) ___ (2) _____ (7) ____ P7 INSTANT ___________________
800 008 (7) _ _ (1) ___ (2) _____ (8) ____ P8 INSTANT ___________________
0 1 2 3 4 5 6 101 009 __ __ (1) ___ (2) _____ (1) ____ P9 ___________________
Default values are shown in ( ) or in bold
D9412GV2/D7412GV2 | Program Record Sheet | RADXPNTS Handler
9.3.8 POPIT Labels
D9412GV2 off-board points are numbered 9 to 127
and 129 to 247. The D7412GV2 uses Points 9 to 75
only. The D9412GV2 reserves Points 128 and 248 for
internal use. POPITs must be connected for Points 129
to 247 to expansion loops connected to POPEX #2.
Two sheets of peel-off POPIT labels are supplied with
the D8125 POPEX Module. Use the sheet marked
“Bank1” for Points 9 to 127. Use the sheet marked
“Bank2” for Points 129 to 247.
Each label has two parts. Place the smaller part (with
only the point number) on the chip. Place the larger
part (with the switch settings) on the base of the
POPIT. Set the switches and cover the POPIT.
Do not program two POPITs for the same point
number. After programming all the points, perform a
Service Walk Test. The D9412GV2/D7412GV2/
D7212GV2 Installation and Troubleshooting Quick Reference
Guide (P/N: F01U003638) contains instructions for
performing a Service Walk Test. If a point does not
test, check the programming for a duplicated address.
Walk Test and Service Walk Test Do Not Show
Extra Points: If the point assignment switches on a
POPIT or OctoPOPIT are set incorrectly, it can create
both missing and extra points. If the same point
number is assigned to two or more POPITs or
OctoPOPITs, none of the points with that number test
correctly. Refer to Section 9.1 Point (Zonex) Bus:
D9412GV2 Terminals and D7412GV2 Terminals on page
34.
9.4 D8128D OctoPOPIT Module
Modules D8128, D8128A, or D8128B are
incompatible with the D9412GV2 or
D7412GV2. Use only the D8128D
OctoPOPIT Module. Using Modules D8128,
D8128A, or D8128B can cause intermittent
Missing and Restoral Reports.
9.4.1 Description
The D8128D OctoPOPIT Module combines the
functions of the D8125 POPEX Module and the
D8127/D9127 POPIT Modules to provide eight off-
board points in a single module. You can wire both
D8128D OctoPOPIT and D8125 POPEX Modules in
parallel to the Zonex Bus terminals on the same control
panel.
Review Section 6.0 Power Outputs on page 25 to ensure
there is enough power for the OctoPOPITs and other
powered devices that will be connected to the system.
Up to thirty D8128D Modules can be connected to the
D9412GV2 Control Panel. A maximum of nine
D8128Ds can be connected to the D7412GV2 Control
Panel (three points can be used on the last
OctoPOPIT).
9.4.2 Listings
The D8128D OctoPOPIT Module is UL Listed for
Local or Police Connected Burglary Alarm, Central
Station Burglary Alarm, Household Burglary Alarm
applications, and commercial fire applications (UL 864
and NFPA 72).
Comments to this Manuals