D9412GV4/D7412GV4/D7212GV4 | Owner's Manual Supplement
8 Bosch Security Systems, Inc. | 9/11 | F01U245224-02
2.5.2 Using Passcode Controlled Menus
On a D1255 Keypad
1. Press the [ESC] key. The keypad shows ENTER PASSCODE.
2. Enter your passcode by pressing the passcode digits followed
by the [ENT] key. The first menu item for which you have
authority appears.
On a D1260 Keypad:
1. Press the Menu softkey in the lower right corner. The keypad
shows ENTER PASSCODE then press [ENTER].
2. Enter your passcode by pressing the passcode digits followed
by the [ENTER] key.
The first and second menu items for which you have authority
appear.
2.6 Walk Tests
2.6.1 Description
The D9412GV4, D7412GV4, and D7212GV4 have three Walk Test
menus that allow the user to test various points that are within
the scope of the keypad without sending a report to the central
station.
When performing a Walk Test, the Walk Test menu indicates that
the menu is ready to time out, and clearly indicates on all keypads
in the area of operation that a test is in progress. Additionally, the
Walk Test procedure issues point trouble conditions for any 24-hr
or fire points that remain off-normal when the Walk Test menu
exits. After the system annunciates the trouble condition, faulted
points are automatically swinger shunt bypassed regardless of the
point index settings. These features are always enabled and have
no configuration parameters. The warning tones commence 5 min
prior to timeout.
Test each smoke detector according to the manufacturer’s
instructions.