Bosch DIP-7082-8HD Installation Manual Page 23

  • Download
  • Add to my manuals
  • Print
  • Page
    / 72
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 22
Replacing the power distributor
Redundant server chassis that are 2U or greater require a power distributor. The power
distributor provides failover and power supply redundancy.
To replace the power distributor:
1.
Turn off the unit and remove the plug from the wall socket or power strip.
2. Remove all cable connections to the power supply from the motherboard, backplane, and
other components. Also, remove both power supplies.
3. Locate the power distributor between the power supply and the fan row.
4. Remove the three screws securing the power supply.
5. Gently pull the power distributor from the chassis. Gently guide all the cables through the
power distributor housing.
6. Slide the new power distributor module into the power distributor housing. Make that
you slide the cables through the bottom of the housing.
7. Reconnect all the power cables, replace the power supply, and insert the plug into the
wall.
3.11.2
DIVAR IP 7000 2U Chassis setup and maintenance | en 23
Bosch Sicherheitssysteme GmbH Installation Manual 2013.09 | V2 | DOC
Page view 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 71 72

Comments to this Manuals

No comments