SECTION 9
PELCO PROTOCOL MODE
9.1 Description
The Pelco Protocol Mode provides support for Pelco-P and
Pelco-D protocols, and is incorporated in AutoDome firmware
version 5.31 and higher. It features Auto Baud Detection which
automatically detects and adjusts the AutoDome protocol and
baud rate to match the controller’s.
9.2 Hardware Configuration
9.3 RS-485 Setup
To use the Pelco Protocol Mode, the AutoDome must be
configured for RS-485 operation.
1. Set the AutoDome configuration dipswitch #2 to ON.See
SECTION 1 and SECTION 2.
2. Connect the RS-422 controller Tx+ terminal to the
AutoDome’s RxD terminal.
3. Connect the controller’s Tx- terminal to the AutoDomes
TxD terminal. See SECTION 1 and SECTION 2.
Both the Pelco controller and AutoDome must be configured
before connecting the devices together. The AutoDome will
respond to Bosch OSRD, Pelco-D, and Pelco-P commands.
The Pelco Mode only supports RS-485 protocol. It
will not transmit reponses to commands it receives.
9.4 Set Addresses
Addresses 0 to 9998 are available for Bosch OSRD
commands.
An AutoDome with an address set to 0 will respond to
commands sent to any address.
Pelco-P protocol must use addresses 1-to-32.
Pelco-D protocol must use addresses 1-to-254.
An AutoDome that was previously configured with an
address above 32 (Pelco-P upper limit) or 254 (Pelco-D
upper limit) can be used without re-addressing the
unit. However, care must be taken that no two
addresses are repeated.
For example:
Pelco-P addresses above 32 are repeated in multiples of
32 (1, 33, 65, 97 are the same).
Pelco-D address above 254 are repeated in multiples of
254 (1, 255, 509, 763 are the same).
9.5 Software
AutoDome firmware 5.31 or higher must be installed for Pelco pro-
tocol mode to operate. Procedures for uploading a new AutoDome
firmware must be followed to successfully install an upgrade.
Only a Bosch VP-CFGSFT firmware upload tool (sold
seperately) can be used to install a firmware upgrade to
the AutoDome.
9.6 Commands
The Pelco Set-Preset command is used by AutoDome to set
Presets 1 through 99. Some Presets have special meaning and
override the normal preset function as follow:
Special Preset Commands
SET A PRESET To set a Preset press and hold the
[PRESET] button for 2 seconds.
92-PRESET Sets the Left Pan limit for an AutoScan
with Limit Stops enabled.
93-PRESET Sets the Right Pan limit for an AutoScan
with Limit Stops enabled.
95-PRESET Invokes the Setup Menu.
GO TO A PRESET To go to a Preset momentarily press and
release the [PRESET] button.
33-PRESET Pans the AutoDome 180 degrees (Flip).
34-PRESET Goes to Zero Pan.
94-PRESET Initiates a Preset Tour
96-PRESET Stops a scan.
97-PRESET Initiates FastAddress (Pelco Random
Scan)
98-PRESET Toggles the Sync Mode between Line
Lock and Crystal (Pelco Frame Scan).
This command is only accessible for
2 minutes after power is applied and
then reverts to normal Preset
functionality.
99-PRESET Start an AutoScan. (User can enable or
disable Limit Stops in the Setup Menu
for AutoScan.)
Some Pelco controllers do not support all Preset
numbers. Consult the specific Pelco controller’s
documentation for supported Presets.
Section 9
EN
© 2005 Bosch Security Systems Page 20 of 40
Page view 19