D9412GV2/D7412GV2 | Operation and Installation Guide | 9.0 Off-Board Points
46 Bosch Security Systems, Inc. | 7/09 | F01U003641-04
9.4.2 Listings
The D8128D OctoPOPIT Module is UL Listed for
Local or Police Connected Burglary Alarm, Central
Station Burglary Alarm, Household Burglary Alarm
applications, and commercial fire applications (UL 864
and NFPA 72).
The D8128D is also suitable for fire supervisory
applications, such as indicating circuit supervision
(using the D192G Bell Circuit Supervision Module),
sprinkler supervision, and valve tamper protection.
Requirements for Fire Initiation Applications
Non-powered, fire initiating devices such as
pull-stations, heat detectors, and UL Listed
four-wire smoke detectors can be
connected directly to the point inputs on the
D8128D.
For UL 864 Commercial Fire applications,
refer to Installing Combination Fire and
Intrusion Alarm Systems in the
D9412GV2/D7412GV2 Approved
Applications Compliance Guide
(P/N: F01U003639) for important
information about combination fire and
intrusion systems.
The D125B Dual Powered Loop Interface Module or
the D129 Dual Class “A” Module zone outputs can be
connected directly to the point inputs on the D8128D.
Use the D125B to connect two-wire smoke detectors.
Typically, the D129 is used for connecting waterflow
switches.
The D125B or D129 and the OctoPOPIT can be
mounted in the same enclosure with the control panel
or in a separate enclosure connected to the control
panel’s enclosure by a conduit not more than 6 m
(20 ft.) in length.
Figure 20: D8128D OctoPOPIT Layout
23451 678
P O I N T S
1
2
3
4
1 - Molex
®
connectors
2 - Address DIP switches
3 - Terminal strip
4 - Point DIP switches
Page view 45