D9412GV2/D7412GV2 | Operation and Installation Guide | 12.0 SDI Devices
64 Bosch Security Systems, Inc. | 7/09 | F01U003641-04
Figure 31: D9133 Jumper Setting for Address
80
1234
80
The DX4010i has specific DIP switch settings for SDI
Address 80 when home or building automation is
desired. Figure 32 on page 64 shows the correct
settings for Address 80.
Figure 32: DX4010i DIP Switch Settings
SER
RxTx
BUS
Rx Tx
LED
ENABLE
DB9 GND
ENABLE
P1
P6
P2
P3
1 2 4 8 16 32 64 128
ON
123456
78
1 2 4 8 16 32 64 128
ON
123456
78
1
2
3
4
1 - Address DIP switches
2 - OFF position
3 - ON position
4 - SDI Address 80 switch settings
12.5.3 Supervision
Supervision of the serial interface module is available
through programming. Supervision is not required to
use a DX4010i or a D9133.
If supervised, and the serial interface module does
not respond to control panel supervision polls, the
control panel sends an SDI Failure Report to the
receiver. If it fails to communicate with the DX4010i or
the D9133, SERVC SDI 80 displays at the keypad.
The SDI Failure Report includes the address of the
troubled module indicating which module needs
service.
12.6 SDI Address 88
SDI Address 88 is available with the D9412GV2 and
D7412GV2 Control Panels and is used for several
different applications. When using SDI Address 88,
connect only one listed device at a time.
12.6.1 D9133DC Direct Connect Programming
Module
Use the D9133DC Direct Connect Programming
Module to handle local programming of the
D9412GV2 and D7412GV2 Control Panels. In
addition, the D9133DC allows diagnostic and history
retrieval.
D9133DC is not UL Listed, and cannot
remain connected to the system for UL
applications.
Connecting the D9133DC
1. Configure D9133DC for SDI Address 88. To
program the control panel when the reset pin is in
the unlocked position, program Enable SDI RPS
to Yes in the GV2AUX handler.
2. Connect D9133DC to Com Port 1 or Com Port 2
on the PC. The D9133DC has a DB-9 female
serial connector. A null-modem cable must be
purchased separately to connect the D9133DC to
a PC.
3. Using 0.8 mm (22 AWG) or 1.2 mm (18 AWG)
wire, connect the D9133DC SDI terminals (SDI
PWR, SDI A, SDI B, and SDI COM) to the control
panel’s SDI terminals (Terminals 29 to 32).
To send or receive the control panel’s program, place
the Reset Pin in the Locked or Unlocked position.
Locking the Reset Pin when
programming the control panel improves
the uploading and downloading times.
Used as an External Modem
The D9133DC can operate as an external modem
when using Remote Programming Software (RPS)
with the control panel. Refer to the
D9412GV2/D7412GV2 Program Entry Guide (P/N:
F01U003636) for programming details.
12.6.2 Network Interface Modules
The Bosch Security Systems, Inc. DX4020 Network
Interface Module and D9133TTL-E Network Interface
Module are four-wire powered SDI devices that
provide connection for two-way communication over
Ethernet networks to D9412GV2 and D7412GV2.
For programming information on enhanced
communications, refer to the D9412GV2/D7412GV2
Program Entry Guide (P/N: F01U003636).
The DX4020 can be installed up to 305 m (1000 ft)
from the control panel using 0.8 mm (22 AWG) wire.
The D9133TTL-E can be installed up to 305 m
(1000 ft) from the control panel using 1.2 mm
(18 AWG) wire.