Bosch TSTBM3H2CPH6W-A Installation Manual Page 15

  • Download
  • Add to my manuals
  • Print
  • Page
    / 32
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 14
6 720 220 376
Revised 02-13 Subject to change without prior notice
15TSTBM3H2CPH6W-A
Tech Setup Steps
LCD will show Adjustment Options
Factory
Default
Settings
Filter
Change
Reminder
This feature will ash FILT in
the display after the elapsed
run time to remind the user
to change the lter. A setting
of OFF will disable this
feature.
You can adjust the lter change
reminder from OFF to 2000 hours of
runtime in 50 hour increments.
OFF
Room
Temperature
Calibration
This feature allows the
installer to change the
calibration of the room
temperature display. For
example, if the thermostat
reads 70° and you would like
it to read 72° then select +2.
You can adjust the room temperature
display to ready -4°F to +4°F above or
below the factory calibrated reading.
0 ºF
Minimum
Compressor
On Time
(min)
This feature allows the
installer to select the
minimum run time for the
compressor. For example,
a setting of 4 will force
the compressor to run for
at least 4 minutes every
time the compressor turns
on, regardless of the room
temperature.
You can select the minimum
compressor run time from “off, “3”,
“4”, or “5” minutes. If 3, 4, or 5 is
selected, the compressor will run
for at least the selected time before
turning off.
OFF
Compressor
Short Cycle
Delay
(min)
The compressor short
cycle delay protects the
compressor from “short
cycling”. This feature will not
allow the compressor to be
turned on for 5 minutes after
it was last turned off.
Selecting ON will not allow the
compressor to be turned on for
5 minutes after the last time the
compressor was on. Select OFF to
remove this delay.
ON
Cooling
Swing
The swing setting,
often called “cycle
rate”, “differential” or
“anticipation” is adjustable.
A smaller swing setting will
cause more frequent cycles
and a larger swing setting will
cause fewer cycles.
The cooling swing setting is adjustable
from ±0.2°F to ±2°F. For Example: A
swing setting of 0.5°F will turn the
cooling on at approximately 0.5°F
above the setpoint and turn the
cooling off at approximately 0.5°F
below the setpoint.
See Temperature swing example after
the Tech Setup Section
0.5 ºF
Heating
Swing
The swing setting,
often called “cycle
rate”, “differential” or
“anticipation” is adjustable.
A smaller swing setting will
cause more frequent cycles
and a larger swing setting will
cause fewer cycles.
The heating swing setting is
adjustable from ±0.2°F to ±2°F. For
Example: A swing setting of 0.5°F will
turn the heating on at approximately
0.5°F below the setpoint and turn the
heating off at approximately 0.5°F
above the setpoint.
See Temperature swing example after
the Tech Setup Section
0.4 ºF
Technician Setup Menu
Page view 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 31 32

Comments to this Manuals

No comments