Expansion
relief
Valve
Non
return
Valve
Primary
Pump.
Davey
SB30-25
or
equivalent
Isol. valve
Isolating
valve
500 - 600 kPa Pressure
Limiting valve
Non return
valve
Pressure & Temperature
Relief Valve or Valves in
accordance with AG102
& as required by State
Regulations. Two 20 mm
PTR Ports provided
Tempering or Thermostatic Mixing valves as required
for Safety Temperatures in areas used primarily for the
purposes of personal hygiene as defined in AS3500 or
by Industry or local regulations
Isol. valve
Bosch
Model
17E or
21E or
25E or
32E
External or Internal Bosch Continuous Flow
Water Heater(s). Manifolded if required in
accordance with manufacturers
recommendations. PTR valves in
accordance with AG102 & as required by
State Regulations.
240 V at C2 Accumulator
Provides pump power &
control via Thermostat.
Thermostat
set to 60 –
70 C
3
2
1
All hot & cold water supply
pipework shown in this
diagram to be sized and
installed in accordance with
AS3500 and local and industry
regulations to ensure adequate
flow to the buildings outlets.
This design shows
3 building outlets
numbered 1, 2 & 3
for illustrative
purposes only
Everlast C2 Accumulator
LEGEND :
Cold Water
Supply
Hot Water
Supply :
Primary
Circuit :
Cold Water Supply
Usually Mains
Pressure.
DIAGRAM 2. WATER MAINS PRESSURE plus PRIMARY CIRCUIT
C:\Documents and Settings\Matt\My Documents\Business\everlast\content\commerical_315C250_MANUALandWarranty.doc Page 5 of 12 January, 2006 Revision 3