6 720 644 887
Error codes
51
Primary fan rotation too low in
operation.
1. Reset errors, disconnect power supply cord and check wire
connection on back side of fan and the connectors on the control
board, see
Fig. 84
,
page 66
.
2. Check supply voltage. It must be 120VAC and properly
grounded.
3. Check that venting meets installation specifications. Long vent
lengths, venting with more than three elbows, blocked vent or
combination venting may cause this failure.
4. Ensure intake and exhaust terminations maintain the required
minimum clearances. Cross contamination between intake and
exhaust may cause the fan to alter its rotational speed.
5. Check gas pressure. Low gas pressure may cause the fan to
change its speed to meet desired temperature.
6. Possible defective control unit call Bosch Water Heating for
further instructions.
No rotational speed sensor signal
from primary fan.
1. Reset errors, disconnect power supply cord and check wire
connections on back side of primary fan and the two connectors
on the control board, see
Fig. 84
,
page 66
.
2. Check supply voltage. The heater must be connected to
120VAC on a properly grounded dedicated outlet.
3. Possible defective component in fan or defective control unit
call Bosch Water Heating for further instructions.
(Flashing) Water flow signal over specified
maximum value.
Water flow > 10 gallon/min.
(Status message).
1. Disconnect power supply cord and check wire connections on
water valve and the two connectors on the control board, see
Fig.
84
,
page 66
.
2. Excessive water pressure and flow. Ensure water pressure is
less than 150psi and flow rate is below 10 gallons per minute.
Over-temperature detected by
outlet temperature sensor.
Temperature > 203°F
1. Check that the outlet sensor is firmly attached to the vertical
section of the hot water pipe, see
Fig. 83
,
page 65
.
2. Check red wire connections at hot water temperature sensor.
Clean terminals with an eraser. If badly corroded, replace sensor
and wire harness.
3. In areas where water has a high mineral content, periodic
descaling may be necessary. See chapter
6.3
,
page 41
for
directions.
4. Check sensor (ref.
page 54, chapter 9).
Cold water temperature sensor
fault.
1. Check connector on wires coming from top of watervalve for a
secure connection. See
Fig. 77
,
page 58
.
2. Sensor may trip if water temperature drops below 36°F (2
°
C).
Protect heater from freezing conditions as any damage due to
freezing conditions is not covered under warranty.
3. Measure sensor resistance (ref.
page 55, chapter 10).