Bosch B450 Specifications Page 32

  • Download
  • Add to my manuals
  • Print
  • Page
    / 48
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 31
ID Parameter Values Description
20 SMS Configuration 0 = Disabled
1 = Enabled
Allows the B450 to be configured via SMS
configuration.
65 IPv4 DNS Server IP
Address
IPv4 address format (0.0.0.0) The B450 uses the DNS server addresses supplied
by the cellular network when the Primary DNS
Server address option is configured as 0.0.0.0. If
the address is not configured as 0.0.0.0, the B450
installs the Primary DNS Server address.
66 Alternate IPv4 DNS
Server IP Address
IPv4 address format (0.0.0.0) If the address is not configured at 0.0.0.0, the B450
installs the Alternate DNS Server address.
67 Panel Programming
Enabled
0 = Disabled
1 = Enabled
Select to enable or disable control panel
programming. This enables/disabled configuration
of the B450 by the control panel.
68 Reporting Delay for
Low Signal
Strength
0 – 3600 sec. (1800) Sets the duration of time when the B450’s signal
strength is measured. The value selected
determines how long the signal strength must be at
a low condition before reporting as low, or how
long the signal strength must be normal before
reporting as normal.
69 Reporting Delay for
No Towers
0 – 3600 sec. (1800) Amount of delay before the module reports a
trouble for not being able to receive signals from a
cell tower.
70 Reporting Delay for
Single Tower
0 – 3600 sec. (0) Amount of time delay before module reports a
trouble due to getting signals from only one tower
instead of multiple towers.
71 Modem Reset
Count
0 – 99 communication attempts
(5)
This parameter determines how many times a
packet of data must be sent without a reply before
the cell module modem is reset to attempt
restoring communications.
72 TCP Keep Alive
Time
0 – 255 sec (45) This parameter determines how long to wait
between transmissions to keep an idle TCP
connection to a remote host from terminating due
to inactivity.
Table 5.5: SMS and USB configuration parameters
Short Message Service (SMS) configuration
The B450 supports configuration by SMS connection. The Short Message Service feature
allows an installer to configure the B450 through the use of a mobile phone, or any other
service that sends compatible SMS text messages.
Use SMS to configure the B450
The SMS string follows a specific format. If the configuration message exceeds 160
characters, you must send multiple messages. Refer to Compose the Configuration SMS for
more details.
When the B450 receives the final valid part of an SMS message, it accepts the configuration.
5.4
5.4.1
32 en | Configuration
Conettix Plug-in Communicator
Interface
2013.09 | 02 | F.01U.282.875 Installation and Operation Guide Bosch Security Systems, Inc.
Page view 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 47 48

Comments to this Manuals

No comments