Bosch INTEGRUS Service Manual Page 59

  • Download
  • Add to my manuals
  • Print
  • Page
    / 90
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 58
Integrus Configuration | en 59
Bosch Security Systems B.V. Installation and Operation manual IOM-INT | V1.1 | 2010.12
7.4.1 System with one transmitter
There are two ways to determine the delay switch positions:
Measuring the cable lengths
Using a delay measuring tool
Both methods are described in the next sections.
Determining delay switch positions by measuring the cable lengths
Use the following procedure to determine the delay switch position based on cable lengths:
1. Look up the cable signal delay per meter of the used cable. The manufacturer specifies
this factor.
2. Measure the lengths of the cables between the transmitter and each radiator.
3. Multiply the lengths of the cables between the transmitter and each radiator with the
cable signal delay per meter. These are the cable signal delays for each radiator.
4. Determine the maximum signal delay.
5. Calculate for each radiator the signal delay difference with the maximum signal delay.
6. Divide the signal delay difference by 33. The rounded off figure is the signal delay switch
position for that radiator.
7. Add delay switch positions for radiators under a balcony, if applicable (see section
7.4.3 ).
8. Set the delay switches to the calculated switch positions.
Figure 7.3 and Table 7.1 illustrate the calculation of the cable signal delay.
Figure 7.3 System with five radiators and measured cable lengths
NOTICE!
The delay switch calculation tool eases the calculation of the delay switch positions.
NOTICE!
For systems with a cable length difference of more than 50 meters, it is recommended to use
a measurement tool to determine the delay differences in order to calculate the delay switch
positions.
20m
20m
30m
30m
R2
R5 R4
R3
R1
20m
Page view 58
1 2 ... 54 55 56 57 58 59 60 61 62 63 64 ... 89 90

Comments to this Manuals

No comments