Bosch DOMESTIC HOT WATER HEAT PUMP User Manual

Browse online or download User Manual for Heat pumps Bosch DOMESTIC HOT WATER HEAT PUMP. Bosch DOMESTIC HOT WATER HEAT PUMP User manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - GREENSOURCE

UK/IEUSER MANUALAIR TO WATER HEAT PUMP WITH DOMESTIC HOT WATER DISTRIBUTION UNITGREENSOURCE6 720 641 467-00.1I6 KW, 7 KW AND 9.5 KW6 720 642 344 (2010

Page 2 - TABLE OF CONTENTS

CONTROL PANEL6 720 642 344 (2010/01)106 CONTROL PANELAll settings are made and possible alarms are displayed via the control panel. The control panel

Page 3 - 1.2 SAFETY PRECAUTIONS

CONTROL PANEL6 720 642 344 (2010/01)116.3 SETTINGSThe function menus are split into different levels to cover various requirements.• Menu Customer lev

Page 4 - 2 THE BENCHMARK SCHEME

CONTROL PANEL6 720 642 344 (2010/01)126.4.3 TEMPERATURESUnder Temperatures displays the current temperatures for the sensors which are most important

Page 5 - 3.2 HEAT PUMP FUNCTION

CONTROL PANEL6 720 642 344 (2010/01)13To set the heat curve:B Select Heat curve in the menu Heating system temperature.B Select the value that is to b

Page 6 - 6 720 615 974-60.1I

CONTROL PANEL6 720 642 344 (2010/01)14B Select Change factor in the sub-menu.B Give the desired value by turning the menu dial. Min = 0, max = 10.B Pr

Page 7 - 4 STANDARD DELIVERY

CONTROL PANEL6 720 642 344 (2010/01)15To enable this function:B Select menu option Remote control.B Select Remote control On.B Change in temperature,

Page 8 - 5 CONTROL UNIT

CONTROL PANEL6 720 642 344 (2010/01)16HOT WATER PEAKFig. 33Regular increase of the DHW temperature The interval for pasteurisation is set in menu Hot

Page 9

CONTROL PANEL6 720 642 344 (2010/01)17Fig. 37B Select Set time and set the time with the menu dial.6.4.9 DISPLAYIn menu Display you can adjust the dis

Page 10 - 6 CONTROL PANEL

MAINTENANCE6 720 642 344 (2010/01)187 MAINTENANCEThe heat pump requires a minimum of maintenance, however, some servicing is still required to get opt

Page 11 - 6.4 MENU

MAINTENANCE6 720 642 344 (2010/01)19Fig. 471 Filter2 Locking ring3 PlugCleaning the filter:B Switch off the heat pump with the ON/OFF switch.B Remove

Page 12 - 4 DHW temperature sensor

TABLE OF CONTENTS6 720 642 344 (2010/01)2TABLE OF CONTENTS1 Explanation of symbols and safety information 31.1 Explanation of symbols . . . . . . .

Page 13

ERROR MANAGEMENT6 720 642 344 (2010/01)208 ERROR MANAGEMENTThe control unit has an advanced monitoring system that gives alarms if anything unforeseen

Page 14

ERROR MANAGEMENT6 720 642 344 (2010/01)218.5 ALARM WINDOW8.5.1 TRIPPED LOW PRESSURE SWITCHFig. 49POSSIBLE CAUSE 1: EVAPORATOR BLOCKED.B Clean evaporat

Page 15

ERROR MANAGEMENT6 720 642 344 (2010/01)228.5.5 T6 HIGH HOT GAS TEMPERATUREFig. 53Possible cause 1: Excessive compressor operating temperature.B Select

Page 16

ERROR MANAGEMENT6 720 642 344 (2010/01)23B Clean filter if required (Æchapter 7.4).POSSIBLE CAUSE 3: PRIMARY HEATING CIRCUIT PUMP FAULT.B Check whethe

Page 17

ERROR MANAGEMENT6 720 642 344 (2010/01)24PROBABLE CAUSE 3; THE UNDER FLOOR HEATING SYSTEM OR RADIATOR VALVES ARE CLOSED:B Open the valves.PROBABLE CAU

Page 18 - 7 MAINTENANCE

SPECIFICATION6 720 642 344 (2010/01)259 SPECIFICATION9.1 FACTORY SETTINGSThe table displays the factory values (F value) of the settings that you, as

Page 19 - 7.6 SNOW AND ICE

SPECIFICATION6 720 642 344 (2010/01)26

Page 20 - 8 ERROR MANAGEMENT

SPECIFICATION6 720 642 344 (2010/01)27

Page 21 - 8.5 ALARM WINDOW

Worcester, Bosch GroupCotswold Way, Warndon, Worcester WR4 9SW.Tel. 0844 892 9900Worcester, Bosch Group is a brand name of Bosch Thermotechnology Ltd.

Page 22

EXPLANATION OF SYMBOLS AND SAFETY INFORMATION6 720 642 344 (2010/01)31 EXPLANATION OF SYMBOLS AND SAFETY INFORMATION1.1 EXPLANATION OF SYMBOLSWARNING

Page 23 - 8.6 WARNING WINDOW

THE BENCHMARK SCHEME6 720 642 344 (2010/01)42 THE BENCHMARK SCHEMEWorcester, Bosch Group is a licensed member of the Benchmark Scheme which aims to im

Page 24

USE6 720 642 344 (2010/01)53USE3.1 GENERAL INFORMATIONWorcester Greensource is a range of heat pumps that draw energy from the outside air for heating

Page 25 - 9 SPECIFICATION

USE6 720 642 344 (2010/01)6Fig. 1 Greensource with HWDU-151 – function description1 Internal unit2 Underfloor heating system3 Radiators4 Heating circu

Page 26 - SPECIFICATION

STANDARD DELIVERY6 720 642 344 (2010/01)74 STANDARD DELIVERY4.1 GREENSOURCE 6-9.5Fig. 2 Heat pump4.2 INTERNAL UNITThe control unit is integrated into

Page 27

CONTROL UNIT6 720 642 344 (2010/01)85 CONTROL UNITThe control unit regulates and monitors the central heating and DHW. The monitoring function shuts d

Page 28

CONTROL UNIT6 720 642 344 (2010/01)95.5.2 WEATHER-COMPENSATED CONTROL WITH ROOM TEMPERATURE DEPENDENCEWeather-compensated control with room temperatur