68 | Fault mode
6 720 644 143 (2010/09)
E9 Heat exchanger temperature limiter or
flue gas temperature limiter has tripped.
B Check heat exchanger temperature limiter and lead for
breaks or short circuits; replace if required.
B Check flue gas temperature limiter and lead for breaks
or short circuits; replace if required.
B Check the operating pressure of the heating system.
B Check temperature limiter; replace if required.
B Check pump starter; replace pump if required.
B Check PCB fuse; replace if required.
B Vent appliance.
B Check heat exchanger on the water side; replace if
required.
B On appliances with displacement bodies in heat
exchanger, check whether displacement bodies are
fitted.
EA Flame not detected. B Check earth lead is correctly connected.
B Check whether gas valve is open.
B Check gas supply pressure; correct if required.
B Check power supply.
B Check electrodes with lead; replace if required.
B Check flue gas system; clean or repair if required.
B Check gas/air ratio; correct if required.
B For natural gas: Check external gas flow limiter; replace
if required.
B For open flue operation, check air supply or ventilation
apertures.
B Clean out condensation trap discharge pipe.
B Remove diaphragm from fan inlet connection and check
for contamination or tears.
B Clean heat exchanger.
B Check gas valve; replace if required.
B Plug in boiler coding card correctly; replace if required.
B Two-phase network (IT): 2 M Ω - insert resistance
between PE and N at PCB power supply.
F0 Internal fault. B Press reset for 3 seconds and release. When the button
is released, the appliance will restart.
B Check electrical plug-in contacts and ignition leads;
replace PCB if required.
B Check gas/air ratio; correct if required.
F1 Internal data error. B Restore Heatronic 3 to standard settings (Æservice
function 8.E).
F7 A flame is detected although the
appliance is switched off.
B Check electrodes; replace if required.
B Check flue gas system; clean or repair if required.
B Check PCB for moisture; dry if required.
Display
code Description Remedy
Table 27 Faults shown on the display