Conettix D6600/D6100IPv6 | Program Entry Guide | UL 864 Required Settings
.
Bosch Security Systems, Inc. | 11/12 | 4998122702-07
3
UL 864 Required Settings
Notice to users, installers, authorities having jurisdiction (AHJ), and other involved parties: This product
incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or
options must be limited to specific values or not used at all as indicated:
Programming
Option
Possible Settings Settings permitted in UL864
Buzzer
-
0:
Buzzer off
- 1: Buzzer on for any events
- 2: Buzzer on for system trouble conditions
- 3: Buzzer on for new events when the automation link fails or
any system trouble conditions occur
- 4: Buzzer on for new events when printer link fails or any
system trouble conditions occur
-
3:
Buzzer on for new events
when the automation link
fails or any system trouble
conditions occur.
Busy Seconds
Reports
- 0: No Busy Seconds Reports
- 1: Busy Seconds Reports for UL applications
- 1: Busy Seconds Reports for
UL applications
External
Parallel Printer
- 1: Primary: All reports go to this device
- 2: Secondary: Reports go to this device only after all primary
devices fail
- 3: Always On: All reports go to this device whether or not it is
functional
- 4: Always Off: Device is disabled. No reports sent to this
device
- 3: Always On: All reports go to
this device whether or not it
is functional
Line Sniff
- 0: Disable phone line supervision
- 1: Enable phone line supervision
- 2: Disable phone line supervision and disable Busy Seconds
Report
- 1: Enable phone line
supervision
CPU
Programmable
Input 1
-
0: The UPS AC Lost signal or the Low Battery signal is not
monitored
- 1: Monitoring the UPS AC Lost signal
- 2: Monitoring the UPS Low Battery signal
D6600:
- 1: Monitoring the UPS AC Lost
signal
D6100IPv6:
- Battery connected:
Setting not required
- Battery not connected:
1: Monitoring the UPS AC Lost
signal
CPU
Programmable
Input 2
- 0: The UPS AC Lost signal or the Low Battery signal is not
monitored
- 1: Monitoring the UPS AC Lost signal
- 2: Monitoring the UPS Low Battery signal
D6600:
- 2: Monitoring the UPS Low
Battery signal
D6100IPv6:
- Battery connected:
Setting not required
- Battery not connected:
2: Monitoring the UPS Low
Battery signal
Duration (Two-
Way Audio)
- 0 to 15
- 0: Disabled
Battery
Supervision
- 0: The UPS AC Lost signal or the Low Battery signal is not
monitored
- 1: Monitoring the UPS AC Lost signal
D6600:
- 0: Battery is not supervised
(UPS is required)
D6100IPv6 (when battery is
used):
-
1: Battery is supervised