4 D6600 Receiver
5 Connection – host PC COM Port to D6600 COM3 port
1
2
3
4
5
6
7
8
9
10
11
4
Figure 14.2: Receiver System – Standard/Network Automation
Callout Description
1 Connection – Host PC Network Interface Card to the Ethernet switch/hub
2 Automation PC
3 Connection – PC COM port to Network Ethernet Module
4 Network Ethernet Module
5 Connection – Network Ethernet Module to switch/hub
6 Switch/hub
7 Connection – Ethernet switch/hub to D600IPv6
8 D6100IPv6
9 Connection – Ethernet switch/hub to Network Ethernet Module
10 Connection – Network Ethernet Module to D6600 COM4
11 D6600
i
Notice!
For automation packages with network capabilities: The packet format received from the re-
ceiver is the same as for RS-232 reporting, except an internet protocol (IP) and user datagram
protocol (UDP) header is stamped on the packet as the data transmitted by either standard
IP or UDP structure over the network. Automation software can easily support the network
communication by calling Socket functions.
74 en | Central Station Automation System