D9412GV3/D7412GV3 | Program Entry Guide | 4.0 Schedules (Skeds) EN | 108
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Table 30: Programming for Two Same Day Opening Windows (refer to Figure 5)
Open Close
W# Day of Week
Early
Begin
Start Stop
Early
Begin
Start Stop
eXcept On
Holiday
Holiday
Index
Area(s)
1
S M T W T F S
06: 00 07 : 00 08: 00 Yes / No 1 2 3 4 1 2 3 4 5 6 7 8
2
S M T W T F S
13 : 00 14 : 00 15 : 00 Yes / No 1 2 3 4 1 2 3 4 5 6 7 8
Do not program a single window to cross the midnight boundary. The window stop time must be later than the
window start time. To program a window that effectively crosses the midnight boundary, you must program two
windows.
For example, to program windows for an area that opens between 11:30 PM and 12:30 AM, five days a week,
use two windows as shown in Table 31.
Table 31: Programming to Link Two Days over Midnight
*
Open Close
W# Day of Week
Early
Begin Start Stop
Early
Begin Start Stop
eXcept On
Holiday
Holiday
Index
Area(s)
1
S M T W T F S
22 : 00 23 : 30 23 : 59 Yes No 1 2 3 4 1 2 3 4 5 6 7 8
2
S M T W T F S
00 : 00 00 : 00 00 : 30 Yes No 1 2 3 4 1 2 3 4 5 6 7 8
* The setting for midnight is 00:00.
W# Close Early Begin
Default: 00: 00
Selection: HH:MM (hours and minutes)
00:00 to 23:59
Close Early Begin: This program item is one of
three required to create a Closing Window. To finish
programming a Closing Window, Close Window Start
and Close Window Stop must be programmed.
The time programmed in the Close Early Begin field
is the earliest time the user can close an area before
the Closing Window Start time. If Opening and
Closing Reports are enabled, arming the area
between midnight and the Close Early Begin time
generates a Closing Report. Additionally:
If A# Disable O/C in Window is set to Yes and
the area is armed between the Close Early Begin
time and the Close Window Start time, the
Closing Event is sent with an Early to Close
modifier. If the Close Early Begin time is the
same as the Close Window Start time, no Closing
Event is sent.
If A# Disable O/C in Window is set to No and
the area is armed at any time, a Closing Event is
sent without the Early to Close or late to Close
modifiers.
Arming the area between the Close Window Start
and Close Window Stop times creates a local event
in the control panel event log, but does not send the
Closing Report to the central station.
Arming the area after the Close Window Stop time
and before the next window’s Close Early Begin time
(or midnight, whichever is earlier) generates a
Closing Event with a Late to Close modifier.
When configuring multiple windows to operate on the
same day, ensure that they are added to the system
in chronological order. For example, if three windows
are programmed to execute on Tuesday, Window 1
(W1) must occur before Window 2 (W2), and Window
2 must occur before Window 3 (W3).
Avoid programming the Open Early Begin
time before a time that is between
another window’s Open Window Start
and Open Window Stop times.
Disabled windows have a beginning time of 00:00. If
the entry for this prompt is 00:00, but times are
programmed for Close Window Start and Close
Window Stop, the window is disabled.
To disable the window, both the hours and minutes
spaces must be 00:00.
00:00 is midnight, 23:59 is 11:59 PM. Make entries
using a 24-hour clock (for example, 7:00 AM is
entered as 07:00, 2:45 PM is entered as 14:45).