Bosch D1257 Installation Guide Page 141

  • Download
  • Add to my manuals
  • Print
  • Page
    / 154
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 140
D9412GV3/D7412GV3 | Program Entry Guide | 6.0 ACCESS CONTROL EN | 141
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
All SDI devices, regardless of area
assigned, report to Area 1, Account 1 by
default upon SDI failure. If a D9210B
becomes disconnected, an SDI Fail ##
and a Missing Point ### Event is
created.
If the D9210B is not programmed with a
D# Entry Area, 9210 NOT READY
appears at the keypad with this door
assigned to it when you press the
[ENTER] key.
D#CC#Scope
Default: 0
Selection: 0 to 8
1 to 8
Determines disarming rights. The
user’s access level and the CC #
Scope determines which areas are
disarmed.
0 Only the area assigned to the D#
Entry Area disarms this door.
Enter the keypad number (CC#) which determines
the scope of the user ID’s disarming rights. Areas
disarm on the basis of this keypad’s scope and the
authority level of the user.
The D# CC# Scope prompt is limited to
the first 8 keypads.
D# Custom Function
Default: 0 (Disabled)
Selection:
0, 128-143 (128-131 on the
D7412GV3)
0
Custom function disabled.
128-143 The custom function number that
executes upon a valid ID, given the
appropriate user access level and
area arm state.
You can program a custom function to run at the
keypad programmed for CC# Scope. This custom
function activates only for users with an L##
Function Level? Assignment (refer to Section 2.10
User Interface on page 76) in which a valid ID can
execute a custom function during the armed or
disarmed state. The user number to which the token
is assigned must have an assigned passcode.
If D# Disarm On Open is set to Yes for the same
door, and L## Function Level? is set to D or C, the
custom function executes when the door is physically
opened.
A user’s access level and the armed state
of the area determine whether the custom
function activates. This access level is
programmed in the L## Function Level?
prompt. Refer to 2.10 User Interface on
page 59.
Table 39 on page 141 shows how this programming
affects custom function activation.
Table 39: Effects of Programming on Custom
Function Activation
L## Function
Level?
Custom Function Activation
M
(Armed)
User token activates the custom
function assigned to the Door
Controller only while the entry area
for the Door Controller is Master
Armed or Perimeter Armed.
D
(Disarmed)
User token activates the custom
function assigned to the Door
Controller only while the entry area
for the Door Controller is disarmed.
C
(Armed and
Disarmed)
User token activates the custom
function assigned to the Door
Controller regardless of the armed
state of the entry area.
-
User token does not run the custom
function assigned to the Door
Controller.
A user’s security level must have an M,
P, or D to operate the custom function.
D# Door Point
Default: 0
Selection:
0 to 127, 129 to 247(0 to 75 on the
D7412GV3)
1 to 127,
129 to 247
The point number assigned to this
door. Points 128 and 248 are
reserved by the control panel for
internal use.
0
No point number is assigned to this
door.
Enter the point number assigned to this door. This
point cannot be used for any other point
assignments.
Page view 140