D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 22
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
User Reports
Selecting Yes enables a report to be sent when the
event occurs.
Table 11: User Reports
Report Selections
Report
Description
R# Point
Bypass
Yes, No Point Bypass Event
R# Forced
Point
Yes, No Forced Point Event
R# Point
Open
Yes, No
Point Opening
Event
R# Point
Close
Yes, No Point Closing Event
R# Forced
Arm
Yes, No Point Force Armed
R# Fail To
Open
Yes, No Fail to Open Event
R# Fail To
Close
Yes, No Fail to Close Event
R# Ext Clos
Tm
Yes, No
Extend Close Time
Event
R# Opening
Report
Yes, No Opening Events
R# Forced
Close
Yes, No
Point Forced Close
Event
R# Closing
Report
Yes, No Closing Events
R# FC
Perimeter Inst
Yes, No
Forced Close
Perimeter Instant
Armed Event
R# FC
Perimeter
Delay
Yes, No
Forced Close
Perimeter Delay
Armed Event
R# Perimeter
Inst Arm
Yes, No
Perimeter Instant
Armed Event
R# Perimeter
Delay Arm
Yes, No
Perimeter Delay
Armed Event
R# Send User
Text
Yes, No User text
Test Reports
To meet UL 864 requirements for
Central Station and Remote Station
applications, enable Test Reports.
Sending Test Reports
Automatic: To send a single Test Report (R# Test
Report) automatically, enable Sked Function Code #9
(Test Report) in the Skeds section of the program.
Refer to Table 12.
Manual: To send a single Test Report manually, enter
[COMMAND][4][1] at the keypad. Refer to the Send
Report prompt on page 62.
To expand this Test Report to include any off-normal
point condition or other off-normal system conditions,
Expand Test Report (refer to page 14) must be
programmed Yes. Refer to the footnotes with Table 13
on page 24 for a list of event types that are included in
an expanded test report. Additionally, the expanded
test report includes Summary Fire Supervisory,
Summary Fire Fault, Summary Controlled Point Fault,
and Summary Point Device Fault conditions.
The control panel can generate an Expanded Off-
Normal Test Report by using Sked Function Code 28
or a Non-Expanded Off-Normal Test Report using
Sked Function Code 29. To generate this event, one
or more points must be in an off-normal state at the
time the Sked executes. Expanded Off-Normal Test
Reports include the Off Normal Test Report Event as
well as a panel-wide summary of off-normal point and
system conditions. Non-Expanded Off-Normal Test
Report Events are sent only when a point is in the off-
normal state but sends only the Off-Normal Test
Report Event.
Sending Status Reports
Automatic: To send a Status Report automatically
that includes the events shown in the footnotes in
Table 12, enable Sked Function Code #10 in the
Skeds section of the program.
Manual: To send a Status Report manually that
includes the events shown in the footnotes in Table
12, enter [COMMAND][4][2] at the keypad. Refer to
the Send Report prompt on page 62.
Sending off-normal conditions as a Status Report
following a Test Report is required by some
automation systems. Sending off-normal conditions as
a Non-status Report that follows a Test Report is
required for other automation systems.
An off-normal condition is any point that is missing,
trouble, supervisory, or in alarm. Also, points not
cleared at the keypad report as off-normal.