D9412GV3/D7412GV3 | Program Entry Guide | 2.0 Panel and Area Wide Parameters EN | 32
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
P## Point Event
Default: Refer to the program record sheet
Selection:
Yes or No
P## Usr Chng Evt
Default: Refer to the program record sheet
Selection:
Yes or No
2.6 RPS Parameters
Use these program items to enable remote
programming software (RPS) functions in the control
panel using the on-board phone connection or a
Network Interface Module. Refer to Section 5.4 SDI
RPS Parameters on page 126 for more information
on these types of remote programming.
2.6.1 Uploading and Downloading Reports
If the control panel is programmed to send reports in
ModemIIIa
2
reporting format, when RPS contacts the
control panel and the passcode is incorrect, the
control panel sends an RPS Access Fail Report to
the central station receiver. RPS Access Fail might
indicate a wrong RPS passcode when
communicating with the control panel, or a valid RPS
session was abnormally terminated.
RPS ACCESS OK is sent according to phone routing
when a Disconnect command is entered from RPS to
terminate the call.
When a Reset Panel is used to terminate the call, a
Remote Reset Report is sent to the central station
receiver, and an RPS ACCESS OK is placed into the
control panel’s event log. Reports in the event log
that were not sent before the Reset Panel are never
sent to the central station receiver.
When RPS programming changes parameters, a
Parameters Changed Report is sent to the central
station receiver. If any programming changes are
made, perform a Reset-bye.
When RPS contacts the control panel, the RPS
passcode and DataLock code are verified. If the
control panel’s passcode matches and the DataLock
code does not, the control panel still generates a
RPS Access OK Event; however, the session ends
immediately.
To prevent the control panel from answering the
telephone automatically, enter 0 in the Answer
Armed and Answer Disarmed prompts in this
section.
2.6.2 Log Threshold Reports
When the event log reaches the percentage
configured in Log % Full and the control panel is
properly configured, it will contact Unattended RPS
over phone or network.
If communication with RPS is unsuccessful, or if not
properly configured, the control panel generates Log
Threshold and Fail to Call RPS events.
Fail to Call RPS Events are logged only locally. If
properly configured, the control panel makes multiple
attempts to reach RPS before sending the reports. To
enable transmission of the events when the Log
Threshold is reached, set a valid phone number in
RPS Ph (refer to RPS Phone # on page 35)or set a
valid IP address in RPS IP (refer to RPS IP Address #
on page 130).
2.6.3 Panel Initiated Unattended RPS
The control panel will automatically contact
Unattended RPS when the Log Threshold is reached
or when the Contact RPS Sked function is executed.
When the control panel is attempting to contact
Unattended RPS, it will start with two attempts. If the
control panel does not reach RPS on the first two
attempts, it waits 10 min then tries six more times with
a 10-min interval between each attempt. One hour
after the last failed attempt, the control panel starts
contacting Unattended RPS again. It makes two more
attempts then waits 10 min and tries six more times
with 10-min intervals between each attempt before
generating a Fail to Call RPS Report and abandoning
the effort.
If network RPS is configured, then any control panel
initiated attempt to contact Unattended RPS will be
over network. If network RPS is not configured, then
contact will be attempted over the phone.
Manually Initiated Unattended RPS: If properly
configured, an authorized user can initiate contact with
Unattended RPS by entering [COMMAND][4][3] and
advancing the menu until RPS via Phone or RPS
via Network shows. After proceeding through one
of these options, the control panel makes one attempt
to contact Unattended RPS.
RPS Passcode
Default: 999999
Selection:
0 to 9, A to F
(six characters required)
Enter six characters. Do not use a space in the
passcode.
The control panel verifies the remote programming
software at the central station has valid access before
connecting using the RPS passcode.