D9412GV3/D7412GV3 | Program Entry Guide | 5.0 AUXPARM EN | 135
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Example of Retry Count:
An acknowledgment of the heartbeat was not
received within 10 sec. The control panel sends the
next Heartbeat Poll after the first 10-sec ACK wait
period expires. If the central station does not
acknowledge this Heartbeat Poll, the control panel
continues to re-send. When the resend count is
reached, the control panel declares this path as failed
(and generates the Comm Trouble ## Event). The
control panel continues to re-send the Heartbeat Poll
at the original poll rate time until it receives an
acknowledgment, even after declaring a Comm
Trouble.
When the control panel receives acknowledgment
from the central station, the control panel returns to
the normal Poll Rate (which, in this example, is 120
sec).
If more than one SDI Path is used, the control panel
handles them on a successive basis. For example, if
acknowledgment from SDI Path 1 is not received
within 10 sec (using the previous example), the
control panel moves to SDI Path 2 to send its
Heartbeat Poll (and subsequently waits for the ack)
before returning to SDI Path 1 to re-send its
heartbeat.
If Heartbeat Polls are enabled to send by
an SDI path, and the Path # Ack Wait
time is exceeded, a COMM TRBL SDI ##
event occurs. When this condition occurs,
all events routed to this path go
immediately to the backup path
destination.
Entries are made in one-sec increments.
5 min = 300 sec
1 hour = 3600 sec
12 hours = 43,200 sec
18 hours = 64,800 sec
Path # Ack Wait
Default: 13
Selection: 5 sec to 65535 sec
5 to 65535
The control panel waits this amount
of time to receive an
acknowledgment from the central
station.
Determines how long the control panel waits for an
acknowledgment from the central station after a
Heartbeat Poll or an actual event was transmitted.
This prompt is applicable to SDI transmitted events
and Heartbeat Polls. Entries are made in one-sec
increments.
Path # Retry Count
Default: 5
Selection: 0 to 255
0
COMM FAIL RG# SDI ### Events
are not generated.
1 to 255
COMM FAIL RG# SDI ### Events
are generated after resending
Heatbeat Poll the number of times
selected for a given SDI path.
Determines how many times the control panel
resends the Heartbeat Poll before declaring a path
failure and generating a COMM FAIL RG# SDI ###
(RG # = 1 to 4, SDI ### = 88 for Path 1, 89 for Path
2, 90 for Path 3, 91 for Path 4) Event.
If using IP Addresses as the
communication means for UL 864
Commercial Fire applications, program
this parameter as necessary.
The default settings meet or exceed the
UL specifications.
5.5.1 Ant-Replay Security Feature
The Anti-Replay feature is always enabled in the
control panel and must be supported by the central
station receiver.
Anti-replay is a strategy that counters “replay
attacks. This feature prevents a malicious attack that
substitutes a control panel or another network
interface module (NIM) from delivering counterfeit
events over a network in place of events sent by the
actual control panel. A replay attack occurs when
someone records a message sent over the network
by Device A, and replays this message at a later time
while pretending to be Device A.
5.6 SDI RPS/Enhanced
Communications Configuration
This section provides the necessary prompts for
configuring the SDI-Network Interface Module (NIM)
when using it for SDI RPS or SDI enhanced
communication applications.
Supervise SDI 88
Default: No
Selection: Yes or No
Yes
Supervise the network interface
module (NIM) at SDI address 88.
No
Do not supervise the network
interface module (NIM) at SDI
address 88.