D9412GV3/D7412GV3 | Program Entry Guide | 3.0 Points EN | 97
Bosch Security Systems, Inc. | 10/11 | F01U170807-02
Local While Disarmed suppresses all
reports from 24-hour points. Do not use
P## Type 0 for this prompt. Remember
that this option works only for Disarmed
points, and a Type 0 is a 24-hour Always
Armed point. Instead, choose any type
other than 0, and use a point response
that reports an alarm, whether or not the
point is armed. For instance, P## Type 1
and P## Response 9 reports an alarm on
an open or a short (I) whether the area is
armed or not.
Local While Disarmed affects Keyswitch
points. This prompt suppresses
keyswitch (troubles and restorals) and
D279 (alarms, troubles, and restorals).
Do not use this parameter for these
applications.
P## Local While Armed
Default: No
Selection: Yes or No
Yes
Suppress Alarm, Trouble and
Restoral* Reports from this point
while the area to which it is assigned
is armed.
No
Report events occurring from this
point while the area is armed.
* Transmission of Restoral Reports continues if the alarm,
trouble, or bypass (by Sked, RPS, or Swinger bypass)
condition occurred when the area disarmed, and the
point restored.
To meet UL 864 requirements for
Central Station and Remote Station
applications, set this parameter to No.
Allows a controlled point (P## Type 1, 2, 3), to report
Alarms, Troubles, and Restoral Reports only when
the area is disarmed. This prompt does not affect
local annunciation.
Local While Armed suppresses all reports
from 24-hour points. Do not use P## Type
0 for this prompt. This setting works only
for disarmed points. Type 0 is a 24-hour,
always armed point. Choose any Type
other than 0, and use a point response
that reports an alarm whether or not the
point is armed. For instance, P## Type 1
and P## Response 9 reports an alarm on
a trouble or a short whether or not the
area is disarmed.
Local While Armed affects Keyswitch
Points. This prompt suppresses
keyswitch (alarms, troubles, and
restorals) and D279 (opening, closing,
troubles, and restorals). Do not use this
parameter for controlled points that arm
or disarm.
P## Disable Restorals
Default: No
Selection: Yes or No
Yes
Enable Restoral Reports from this
point.
No
Disable Restoral Reports from this
point.
To meet UL 864 requirements for
Central Station and Remote Station
applications, set this parameter to No.
Use this option to disable any Restoral Reports from
this point after it returns to normal from an alarm or
trouble condition.
P## Force Arm Returnable
Default: No
Selection: Yes or No
Yes
This point automatically returns to the
system when it restores to normal.
No
This point stays out of the system
until the area is disarmed.
Use this option to allow points that were force armed
out of the area to return back to the armed state when
they become normal again without having to disarm
the system.
Use on loading dock doors, that must
remain open until loading is completed.
After the loading dock door is closed, the
point detects any subsequent opening
and reports an alarm.