SETTINGS
6 720 806 768 (2013/02)52
20.7 INSTALLER
This section includes:
General
Heat pump x capacity
Connected I/O boards
Compressor working area
Generated energy
Operating times and consumptions
Temperatures
Programmable outputs
Inputs
Outputs
Circulation pumps
Screed drying
> General
>> Anti-seizure mode
>>> Day of the week
>>> Start time
Set date and time for anti-seizure operation.
Anti-seizure mode ensures that components do not become seized
during periods of inactivity.
Anti-seizure mode operates differently in summer and in winter. This
enables the duration of the anti-seizure operation to be reduced.
Furthermore, during anti-seizure operation the entire system does not
need to be switched off in winter.
Anti-seizure mode in summer mode
Anti-seizure mode in winter mode
>> Highest permitted flow temperature T1
>> Operating mode
For a description of operating modes ( Chapter 8.4).
>> Groundwater
Function not used.
>>> Compressor start delay
Function not used.
>> Display light switch off delay
Set the delay before the display backlighting is automatically
switched off after the last display activity (navigating, setting, alarm
display etc.).
>> Time for reset of access level
Set how much time it should take for the control unit to return
automatically from installer level to customer level.
> Heat pump x capacity
The total capacity is selected under Start-up. If an incorrect value was
selected, make changes in line with the heat pump type plate.
> Connected I/O boards
All boards and current version are displayed, if relevant.
Factory setting Wednesday
Alternative Monday-Sunday
Table 113 Anti-seizure day
Factory setting 12:00
Alternative 0:00 - 23:00
Table 114 Anti-seizure start time
Anti-seizure mode starts only if there is no other type of
demand. When there is a demand, the anti-seizure
operation waits for up to one hour for the demand to be
satisfied. Otherwise, the anti-seizure operation has to
wait until the next period.
Heat pump 1 runs first followed by heat pump 2, etc. 3-
way valves and circulation pumps are run for 1 minute
and mixing valves for the respective mixing valve's run
time + 10s. A pause of 30s is made between
components.
During anti-seizure mode, certain parts of the heating
system become hot for a short period of time, which is
completely normal.
The anti-seizure mode is not cancelled if a hot water
demand arises during the anti-seizure operation. The hot
water temperature can thereby fall. A suitable time for
anti-seizure operation is when the hot water
consumption is low, e.g., at night.
In winter mode, anti-seizure operation only operates on
valves, mixers and pumps that normally do not operate
in winter mode (refers to accessories such as pool and
solar). Anti-seizure mode can occur during operation.
Factory setting 80,0 °C
Lowest value 10,0 °C
Highest value 100,0 °C
Table 115 Radiator
Factory setting 45,0 °C
Lowest value 10,0 °C
Highest value 45,0 °C
Table 116 Underfloor
The set operating mode is indicated with the symbol >
before the selected mode. Operating mode is selected
automatically the first time the heat pump is started.
Operating mode can be changed here. The control unit
allows only the options that can be achieved with the
installed equipment.
Selection of operating mode leads to automatic setting
of certain values in the control unit.
Factory setting 5min
Lowest value 1min
Highest value 240min
Table 117 Display light switch off delay
Factory setting 20min
Lowest value 1min
Highest value 240min
Table 118 Reset of access level
Lowest value 6.0kW
7.0kW
9.0kW
11.0kW
14.0kW
1)
1) Not available in UK market.
Highest value 17.0kW
1)
Table 119 Heat pump capacity