SETTINGS
6 720 806 768 (2013/02) 55
>> Heat source
>> Program settings
>>> Flow temperature increase per heating step
>>> Number of days per heating step
>>> Maximum flow temperature
>>> Number of days with maximum temperature
>>> Flow temperature decrease per cooling step
>>> Number of days per cooling step
20.8 ADDITIONAL HEAT
The additional heat works together with the heat pump to maintain the
right heating in the circuits. The additional heat can be selected to work
alone.
Under Additional heat, there are:
Additional heat general
Electric additional heat
Hot water electric heater
Additional heat program
> Additional heat general
Under Additional heat general the functions that are common to
electric additional heat and mixed additional heat are found.
>> Start delay
Set what start delay should apply to the additional heat.
When the need for additional heat arises, a timer with set time is
started. When this time has passed the additional heat starts.
>> Additional heat only
▶Change to Yes if the additional heat should work alone.
This can be suitable if the heat pump should provide heat before, e.g.,
the collector circuit is ready.
>> Block additional heat
Indicate if the additional heat should be blocked. In this case, the
additional heat may not take part. The additional heat is, however,
allowed to kick in in alarm mode and additional heat only mode if no
other blocking function is enabled.
>> Maximum outdoor temperature for additional heat
Set the desired temperature limit. If the outdoor temperature exceeds
this value, the additional heat may not work.
> Electric additional heat
The control unit supports 1 additional heat unit.
The settings for connection capacity and regulator for the additional
heat use are made under this menu.
> Electric heater connection
>> Connected output
Shows the actual output of the input electric additional heat.
Factory setting Additional heat
Alternative Both/Compressor/Additional heat
Table 134 Heat source drying
Factory setting 5.0K
Lowest value 1.0K
Highest value 10.0K
Table 135 Temperature increase per heating step
Factory setting 1
Lowest value 1
Highest value 5
Table 136 Days per heating step
Factory setting 45 °C
Lowest value 25 °C
Highest value 60 °C
Table 137 Maximum flow temperature drying
Factory setting 4
Lowest value 0
Highest value 20
Table 138 Days with maximum temperature
Factory setting 5.0K
Lowest value 1.0K
Highest value 10.0K
Table 139 Temperature decrease per cooling step
Factory setting 1
Lowest value 1
Highest value 5
Table 140 Days per cooling step
CAUTION: Risk of floor damage
Follow the manufacturer's recommendations for the
floor tiles.
See manual for the multi-module for the mixed additional
heat operating mode.
Factory setting 120min
Lowest value 0min
Highest value 240min
Table 141 Additional heat start delay
Factory setting No
Alternative Yes/No
Table 142 Additional heat only
Factory setting No
Alternative Yes/No
Table 143 Block additional heat
Factory setting 10 °C
Lowest value -30 °C
Highest value 40 °C
Table 144 Maximum outdoor temperature for additional heat