64 en | System Informations 2 AMAX panel 2000 / AMAX panel 2000 EN
F.01U.241.127 | V4 | 2011.12 Installation Manual Bosch Sicherheitssysteme GmbH
8.2.1 System Option Programming Definition
If the system programming data is not correct, the keypad beeps to indicate wrong operation
but the data is kept as the same.
When the panel is starting, it will follow the Arm/disarm status before the last time the panel
power was down/reset.
Quick arming starts.
AC MAINS Fault Report is followed with other report or one hour delayed to send out.When
AC MAINS is lost, and battery is lower than 9VDC; or Aux power, keypad power and battery
voltage are lower than 9V+ -5, the system will not send out the report to a remote receiver.
When one of the voltages rises to 10VDC+ -5, the system will wait for one minute to back to
normal work in order to get the stable work status.