19TSTBM3H2CPH6W-ATechnician Setup Menu
Tech Setup Step (Continued from the previous page)
LCD will show Adjustment Options
Factory
Default
Settings
Remote
Sensor
Enables the use of up to four
indoor sensors TSTBM-RRS--
TW-A. Selecting YES requires
the TSTBM3H2CPH6W-A master
thermostat to be powered with
24V on C and R terminals.
When NO is selected the
thermostat is unable to connect to
an indoor remote sensor TSTBM-
RRS--TW-A. When YES is selected
the thermostat is able to connect
to up to four indoor remote
sensors TSTBM-RRS--TW-A. Go to
the next step FINDING SENSOR
to connect TSTBM-RRS--TW-A.
NO
Finding
Sensor
This step connect TSTBM-RRS-
-TW-A to TSTBM3H2CPH6W-A.
The previous step Remote Sensor
must be set to YES in order to
connect an TSTBM-RRS--TW-A.
The number shown represents
the zone Use
or
+
to select the
zone you wish to connect.
The zone setting on the
TSTBM3H2CPH6W-A and the
TSTBM-RRS--TW-A must be the
same to connect.
See TSTBM-RRS--TW-A user guide
for detailed TSTBM-RRS--TW-A
connection information.
See note above on previous page
for more information.
1
Local Temp
Sensor
Disable the sensor on the master.
At least one TSTBM-RRS--TW-A
indoor remote sensor must be
connected to disable the local
TSTBM3H2CPH6W-A sensor.
YES enables local
TSTBM3H2CPH6W-A sensor
NO disables local
TSTBM3H2CPH6W-A sensor
YES
Freeze
Protection
Turns on the heat for 10
minutes each hour if unable
to communicate with the
TSTBM3H2CPH6W-A master
thermostat if there has been a
call for heat in the last 24 hours.
YES enables freeze protection
NO disables freeze protection
NO
Stages of
Heat
(only
available in
HP mode)
You can congure the thermostat
to operate a 3 stage heat pump
system.
2H 2C = 2 heat, 2 cool
3H 2C = 3 heat, 2 cool
This feature only shows if
Technician Setup Step for HEAT
PUMP is set to ON.
Use the
or
+
key to change
between 2 heat and 3 heat.
2 heat will use Y1 as rst stage
and W2 as auxiliary.
3 heat will use Y1 as rst stage,
Y2 as second stage and W2 as
third stage.
2H/2C
Balance
Point
(Requires
TSTBM-OTS-
TW-A and in
HP mode)
Balance point can eliminate the
need for a fossil fuel kit.
An outdoor temperature above
balance point will cause the
thermostat to only allow the
Y terminal(s) to energize. An
outdoor temperature below
balance point will cause the
thermostat to only allow the W2
to energize.
YES
10, 20, 30, 35, 40, 45, 50 outdoor
temperature balance point
setting.
NO
NO