Conventional flue† – minimum air vent area (cm
2
) for
appliances installed in a compartment
Internal ventilation* External ventilation**
kW High level
(D)
Low Level
(C)
High level
(D)
Low Level
(C)
12/18 198 279 99 198
18/25 275 413 138 275
25/32 352 528 176 352
*Internal air to and from a space/room inside the building.
**External air to and from directly outside the building.
Due to changes to BS 5410 and modern building design, these figures no
longer incorporate the adventitious ventilation allowance.
Room-sealed flue† – minimum air vent area (cm
2
) for
appliances installed in a compartment
Internal ventilation* External ventilation**
kW High level
(D)
Low Level
(C)
High level
(D)
Low Level
(C)
12/18 198 198 99 99
18/25 275 275 138 138
25/32 352 352 176 176
Air supply
CF (conventional flue)
An adequate supply of free air must be delivered to the boiler
for combustion purposes through a permanent inlet, such as
an air brick, into the area where the boiler is situated.
Combustion air must not be taken from bathroom or
bedroom areas.
Minimum area of air inlet for combustion*
kW Area
12/18 99cm
2
18/25 138cm
2
25/32 176cm
2
* Due to changes to BS 5410 and modern building design,
these figures no longer incorporate the adventitious
ventilation allowance.
Compartment installation
Internal ventilation External ventilation
Compartment ventilation
A Compartment
B Boiler
C Low level vent
D High level vent
E Air supply
Follow the requirements of BS 5410 and note:
Minimum clearances must be maintained
An access door is required to install, service and
maintain the boiler as well as any ancillary equipment,
i.e. condensate trap
If fi tting the boiler into an airing cupboard use a non-
combustible material to separate the boiler from the airing
space. If the material is perforated, the holes must not
exceed 13mm.
Compartment ventilation
Ventilation must be provided for boilers fi tted into
compartments as described in BS 5410
A minimum of 2 air vents must be fi tted, one at low level
(C) and another at high level (D) onto the same wall using
the same air (E) for circulation
Free air must not be taken from a room or internal space
containing a bath or shower and must not communicate
with a protected area such as a hall, stairway, landing,
corridor, lobby, shaft, etc.
Air vents must allow access for clean, free air and
must be sited to comply with the fl ue terminal
position requirements
Air ducting runs must not exceed 3 metres.
Low level air vents must be within 450mm from
the fl oor
A warning label must be added to the vents with a
statement to the effect: “Do not block this vent.
Do not use for storage”.