Plume management terminal positioning
Door
Balcony
Boundary
Drainpipe
2
4
5
1
600
200
200
300
600
600
300
150
150
150
150
600
Window
Window
25
300
Window
±45°
Flue exhaust
outlet
Air intake
6
100
2,500
7
3
Key to illustration
1. 600 mm distance to a boundary, unless it will cause
a nuisance. BS 5410: Part 1 recommends that care is
taken when siting terminals in relation to boundaries.
2. Internal/external corners the air intake can be reduced
to 150mm providing the flue exhaust outlet has a
300mm clearance.
3. Vertical sanitary pipe: 25mm to the flue air intake and
300mm to the flue exhaust outlet.
4. Clearance no less than 200mm from the lowest point of
the balcony or overhang, installations in car ports are
not recommended.
5. 1,200mm from an opening in a car port on the same wall
i.e. door or window leading into dwelling. 600mm to a
surface facing a terminal.
6. Using a plume management kit, the air intake
measurement can be reduced to 150mm providing the
flue exhaust outlet has a 600mm clearance. Plume kits
running horizontally must have a 10º fall back to the
boiler for proper disposal of condensate.
For details on specific lengths see relevant boiler
Technical & Specification manual.
7. 2,500mm between air intake and facing terminal.
Note
All measurements are the minimum clearances required
Terminals must be positioned so as to avoid combustion
products entering the building
Support the fl ue at approximately one metre intervals
and at a change of direction. Use suitable brackets
and fi ttings.
All measurements in millimetres