D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 42
Bosch Security Systems | 1/04 | 47775E
If a 24-hour point alarms while the area is
disarmed, arming that area with a
keyswitch does not clear the A# Single
Ring flag.
Silencing the bell resets A# Single Ring.
A# Bell Test
Default: No
Selection:
Yes or No
Yes Initiate Bell Test.
No Do not initiate Bell Test.
Provide alarm output from the relay programmed at
A# Alarm Bell
after the Closing Report was
confirmed or the exit delay time expired.
Bell Test After Confirmation
In areas that report opening and closing activity, the
Bell Test happens after the control panel sends the
Closing Report and receives the acknowledgment
from the central station receiver. For proper
operation of the Bell Test after closing confirmation,
the following rules apply:
The control panel must report opening and
closings to the central station.
Restricted openings and closings should not be
used, and Opening and Closing Windows
should not be used.
Area Armed Confirmation
In areas that do NOT report opening and closing
activity, the alarm bell relay output for this area is
activated for 2 seconds after exit time expires.
Multiple Bell Tests occur: When more than
one area is armed at the same time (such as
using the ARM ALL AREAS? function), the
bell rings for 2 seconds with a 2 second
pause between each bell activation if all
areas have the same exit delay time
programmed. Otherwise, the Bell Test
occurs as each area arms and it completes
its exit delay time.
When areas arm simultaneously and report
to the central station, the Bell Test occurs
as the central station receiver confirms each
area.
2.9.5 Open/Close Options
Programming determines if Opening, All Normal
Closing, and Force Arm/Bypass Closing Events are
reported to the remote central station. Without
remote reporting, all control panel and area arming
(Closing Events) and disarming (Opening Events)
default to local events.
Use this programming category to determine which
opening and closing supervision characteristics are
required.
There are three ways to generate reports from the
control panel. You can generate reports by account,
by area, or a combination of both.
To suppress reports:
Use Opening/Closing Windows to suppress
reports for a specified period of time and then
automatically turn them on again.
Use the Restricted O/C options. A Closing
Report is sent if the user is force arming, sending
duress, or bypass arming. An Opening Report is
sent if the user is disarming during an alarm
condition or unbypasses points when disarming.
If the system is normal, no Opening or Closing
Report is sent.
For the scheduled suppression of Opening
and Closing Reports, see Section 5.1.1
Opening and Closing) to define Opening
and Closing Windows.
Account Opening and Closing Reports
Opening and Closing Reports are sent by account
when the last area in a group of areas with the same
account number(s) is armed.
Area Opening and Closing Reports
Closing Reports are sent for each area as it is armed.
The account number is also sent for each area.
Customizing Account Opening and Closing
Reports
You can eliminate area Opening and Closing
Reports from selected areas in the account by
programming
A# Area O/C
No for those areas.