D9412G/D7412G | Program Entry Guide | 2.0 9000MAIN EN | 71
Bosch Security Systems | 1/04 | 47775E
0101
0101
0101
Programming Tip #4:
Fire Trouble Resound was added to
firmware versions 6.20 and later. This
feature, when enabled, resounds the Fire
Trouble condition at 12:00 PM or 12:00
AM if the Fire Trouble condition still exists.
It does not, however, retransmit the Fire
Trouble condition at the specified time.
The Fire Trouble Event is only sent, if
programmed to do so, at the time it
occurs.
To disable the Fire Trouble Resound
feature, program a 0 in Area 6’s Silent
Alarm Relay entry.
To enable the Fire Trouble Resound
feature at 12:00 PM, program a 61 in
Area 6’s Silent Alarm Relay entry.
To enable the Fire Trouble Resound
feature at 12:00 AM, program a 62 in
Area 6’s Silent Alarm Relay entry.
Note:
Programming a value other than 0, 61, or 62
enables the Fire Trouble Resound feature at
12:00 AM.
Beginning in Firmware version 6.30 and
higher, a Fire Trouble Resound prompt
was added to Section 6.7 Miscellaneous.
This prompt operates as described.
0101
0101
0101
Programming Tip #5:
Perimeter Armed Relay was added to
firmware versions 6.20 and later. This
feature, when enabled, turns the Fail to
Close Relay function into a Perimeter
Armed Relay function.
To switch the Fail to Close Relay into a
Perimeter Armed Relay function, program
a 63 in Area 7’s Silent Alarm Relay entry.
Then, program a relay number into the
appropriate area you wish to activate when
the area becomes Perimeter Armed
(COMMAND 2, COMMAND 3, or
COMMAND 8). See Programming Tip #2
for additional information.
2.13.2 Panel-Wide Relays
The following eleven relay options activate when
they occur anywhere in the control panel. They are
not restricted by area boundaries.
AC Failure
Default: Blank
Selection: Blank, 1 to 128 (1 to 64 for D7412G),
A, B, or C
Activates when the control panel responds to an AC
power failure as programmed in
AC Fail Time
in
Section 2.5 Power Supervision. This relay automatically
resets when AC power is restored.
Use this relay as an option to create
audible annunciation using the command
centers for all applications excluding
commercial fire systems.
Battery Trouble
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for D7412G),
A, B, or C
Activates when battery voltage falls below 85% of
capacity (12.1 VDC) for a fully charged (13.8 VDC)
battery, or when the battery is in a missing
condition. This relay automatically resets when
battery power is restored.
Use this relay as an option to create
audible annunciation using the command
centers for all applications excluding
commercial fire systems.
Phone Fail
Default: Blank
Selection:
Blank, 1 to 128 (1 to 64 for D7412G),
A, B, or C
Activates when a telephone line failure occurs. A
time must be entered in Ph Supv Time (see Section
2.2 Phone Parameters) for this relay to activate. This
relay automatically resets upon restoral of the phone
line(s).