Outdoor Vent Termination
When installing the Bosch 32C outdoors, a Vent Cap is
required (code: BCVC-100C).
Vertical Vent Termination
The following considerations must be made when venting
vertically
3 Terminate at least 1.8m from the combustion air intake
of any appliance, and 1m from any other building
opening, gas utility meter, service regulator etc
3 Terminate the vent system at least 600mm above but
not more than 2m above the roof line
3 Provide vertical support every 3.6m of flue
3 Slope the horizontal vent 50mm upwards for every 1m
Horizontal Vent Termination
The following considerations must be made when venting
horizontally
3 Terminate at least 350mm above the ground
3 Terminate at least 2.3m above public walkways, 2m
from the combustion air intake of any appliance, and
1m from any other building opening, gas utility meter
or service regulator
Terminate at least (as per AS/NZS5601):
3 1m above any forced air inlet
3 1.5m below any door, window or non-mechanical air inlet
3 0.5m horizontally from any door, window or non-
mechanical air inlet
3 0.3m above any door, window or non-mechanical air inlet
3 Slope the horizontal vent 50mm upwards for every 1m
3 Use a condensation drain if necessary
12
|
Technical & Specification Information – Bosch 32 Series Water Heaters