Access Control Interface Module Installation | en 21
Bosch Security Systems, Inc. Installation and Operation Guide F.01U.215.244 | 05 | 2012.06
Fill out the Program Record Sheet pages (included in the Program Entry Guide). Be sure the
program record for this door controller contains the area assignment, address assignment
and control center assignment.
The interface module rotary switches provide a TENS and ONES setting for the module’s
address. Set the address by setting the rotary switches based on Section Table 3.4 D9210C
Rotary Switches, page 21. Section Figure 3.6 D9210C Rotary Switches, page 21 shows the
rotary switches settings for address 81.
Figure 3.6 D9210C Rotary Switches
Table 3.4 D9210C Rotary Switches
3.2.10 Connecting Power and SDI
NOTICE!
Whenever possible, be consistent when numbering doors, control centers, and areas. This will
help when programming a system with more than one door. For example, assign Door 1 to
Area 1 and Control Center 1.
Serial Device
Fail mode Central Station
Modem IIIa
2
TENS ONES Control Center
Display
UNLOCKED SDI #33 8 1 D9210 #1
UNLOCKED SDI #34 8 2 D9210 #2
UNLOCKED SDI #35 8 3 D9210 #3
UNLOCKED SDI #36 8 4 D9210 #4
UNLOCKED SDI #37 8 5 D9210 #5
UNLOCKED SDI #38 8 6 D9210 #6
UNLOCKED SDI #39 8 7 D9210 #7
UNLOCKED SDI #40 8 8 D9210 #8
LOCKED SDI #33 9 1 D9210 #1
LOCKED SDI #34 9 2 D9210 #2
LOCKED SDI #35 9 3 D9210 #3
LOCKED SDI #36 9 4 D9210 #4
LOCKED SDI #37 9 5 D9210 #5
LOCKED SDI #38 9 6 D9210 #6
LOCKED SDI #39 9 7 D9210 #7
LOCKED SDI #40 9 8 D9210 #8
CAUTION!
Do not connect 24 VDC or non-isolated [from the strike] 12/24 VAC of the interface module.