Access Control Interface Module Troubleshooting | en 27
Bosch Security Systems, Inc. Installation and Operation Guide F.01U.215.244 | 05 | 2012.06
Reader Action If Reader LED is then Door State is so LED will toggle
Idle reader LED
Red Locked
Red Secured
Green Unlocked
Continuous Red/
Green
Locked on Fail
(Rotary address
switch
optional)Unlocked on
Fail (Rotary address
switch optional)
SDI disconnected,
D9210C is not
programmed with an
area, D9210C faulty.
Access Granted
Red: Valid token to
activate strike.
Locked Red to Green for
duration of strike
time.
Green: Valid token
will not activate strike
because strike is
latched to allow
access.
Unlocked Green to Red to
Green
Access Denied
Red: Valid token
format not added.
Locked Red to Green to Red
(pattern repeats
twice)
Red: Valid token but
level is turned off.
Locked Red to Green to Red
(pattern repeats
twice)
Red: No access
allowed regardless of
level because door is
secured.
Secured Red to Green to Red
(pattern repeats
three times)
Custom Function
Red: Valid token will
run.
Locked/Secured Red to 1 second
Green to Red
Green: Valid token
will run.
Unlocked Green to 1 second
Red to Green
Adding IDs
Red: Adding new
token
Learn Mode while
door is secured or
locked.
Red to 2 second
Green back to Red
Red: Changing token
that exists.
Learn Mode while
door is secured or
locked.
Red to Green to Red
to Green to Red