24 en | Installation Access Control Interface Module
F.01U.215.244 | 05 | 2012.06 Installation and Operation Guide Bosch Security Systems, Inc.
To activate the interface module, follow the instructions in the Program Entry Guide. Use the
ACCESS Program Record Sheet to match the door to the proper address and to ensure that
the door is assigned to the proper area.
3.2.12 Testing the interface module
Description. The interface module comes shipped with a default program that allows a quick
test run upon installing the unit. Go through the following items to verify the interface module
is functioning properly. If problems arise, refer to Section 5 Troubleshooting, page 26
Interface Module. Verify that the Heartbeat LED is pulsing approximately once every second.
This indicates the microprocessor is running. Go to the Unlock Door function. A number from
1 to 8 should appear for the door controller. If an F appears, the unit has failed or is not
responding correctly to the control panel’s polls.
Zone. Using the keypad, verify the point is normal when the door is closed, the point goes off
normal when the door is opened and a shunt is not applied, and that the point stays normal
upon opening the door on a valid access granted.
Strike. Read a valid token to activate the strike. If tokens have not been added, use the Door
Control, Door Unlock mode to cycle the strike. In addition, you will cycle the strike when you
test the [RTE/REX] inputs (if shunt only is not programmed [YES].
RTE/REX. Fault these inputs to activate the strike. The default for the strike time is 10
seconds. Test each separately.
Buzzer. The buzzer should have sounded on each strike activation. Also hold the door open
past the normal shunt time and ensure the Extend Buzz functions.
Reader. Depending on the reader, the reader LED will be red upon powering up the interface
module. During the above tests, it will turn green anytime the strike is activated.
To verify the reader, check that the Reader LED blinks rapidly while a card is passed through
the reader or a token is held up to the proximity reader. Review the instructions that come
with the specific reader for more information on operational use.
NOTICE!
For other LED functionality, refer to Section 5 Troubleshooting, page 26.