Access Control Interface Module Operation | en 25
Bosch Security Systems, Inc. Installation and Operation Guide F.01U.215.244 | 05 | 2012.06
4 Operation
4.1 Door Release Application
The interface module can be used for door release functions. When used in this configuration,
the strike relay contacts must be supervised. This can be accomplished with the use of an
end-of-line relay commonly used for smoke detectors. Connecting the interface module for
this application is shown in the illustration below.
Program Point Index in the POINTS handler as Supervisory with Point Response as [A]
Supervisory on Open and Trouble on Short.
The power supply, end-of-line relay, and the interface module must be in the same enclosure
or adjacent enclosures connected via conduit not longer than 20 feet (6 m).
Figure 4.1 D9210C Door Release Application Connections
NOTICE!
When using the interface module for the Door Release, you must use the D8004 Transformer
Enclosure for the power supply.