Conettix D6600/D6100IPv6 | Program Entry Guide | 2.0 CPU Configuration
.
Bosch Security Systems, Inc. | 11/12 | 4998122702-07
19
2.4.12 SIA Fire Restore
Default: 0
Selections: 0 or 1
0 The automation PC sends a common Fire
Restoral code if programmed for SIA Output
Mode.
1 The automation PC differentiates between
Fire Restoral after Alarm and Fire Restoral
after Trouble, Missing, or Supervisory if
programmed for SIA Output Mode.
All Bosch control panels using the Modem IIe and
IIIa
2
formats differentiate between Fire Restoral after
Alarm and Fire Restoral after Trouble, Missing, or
Supervisory in the message that is sent to the
D6600/D6100. SIA Automation Output Mode can also
differentiate between these two message types, or it
can combine them into a common Fire Restoral
message.
If the Modem IIe Fire prompt is
programmed “0,” the programming of
the SIA Fire Restore prompt has no
effect on the SIA Automation Output
Format.
Table 4: SIA Fire Restore Examples
SIA
Mode
SIA Fire Restore = 0 SIA Fire Restore = 1
FIRE ALM
RESTOR
<header>[#aaaa|NriaF
Rppp]
<header>[#aaaa|NriaF
Hppp]
FIRE TBL
RESTOR
<header>[#aaaa|NriaF
Rppp]
<header>[#aaaa|NriaF
Jppp]
2.4.13 Packet Separator (/)
Default: 0
Selections: 0 or 1
0 Final packet separator is not sent in SIA
automation message.
1 Final packet separator is sent in SIA
automation message.
This prompt enables the final packet separator (/) (in
SIA Output Mode) when messages with event
modifiers are sent to the automation PC.
2.4.14 Sub Subscriber
Default: 0
Selections: 0 or 1
0 Sub subscriber (sub user) data is not sent
to SIA automation output.
1 Sub subscriber (sub user) data is sent to
SIA automation output.
This is a programmable modem format only item that
determines whether the specific access control card
or token number identifier (sub user) is also sent to
the SIA automation output.
2.4.15 Output Format
Default: 1
Selections: 0 to 2
0 COM3 port disabled
1 6500 format (expanded reporting)
2 SIA Computer Interface Standard format
If you disable the COM3 port by
selecting 0 after selecting an automation
output format, you must reboot the
receiver.
Set Menu Item 6.3.7 Device to 2 to use COM3
RS-232 and the output format programmed in
2.5.15 Output Format.
Set Menu Item 6.3.7 Device to 1 to use the output
format programmed in Menu Item 6.3.6 Network
Automation Output Format on page 43.