Central Station Tips
Back-up Receiver
Spare circuit boards and receivers should be available at the central station. Keep a spare kit
on hand. UL Listed central stations monitoring burglary or fire alarms must have a spare
receiver available for activation within 30 sec.
Computer Interface
i
Notice!
Keep spare cards for all receiver components.
Keep a spare CPU terminator card in the central station.
D6200 Programming Software
i
Notice!
Keep D6200 Programming Software in the central station at all times.
Telephone Lines
Emergency Ringers
Extension ringers for incoming receiver telephone lines are available from telephone
equipment supply companies. They ring briefly to indicate an incoming call. If they continue to
ring, your receiver is out-of-service. The ringer has a volume control, but in a high traffic
central station, you might prefer to use beehive lights instead of ringers.
Rotary Lines
i
Notice!
Use rotary receiver lines (hunt groups) to prevent delay in alarm signals during periods of
busy central station traffic
Rotary lines are also important for providing alternate paths when a line is out of service. To
use this feature have your dispatcher dial the out-of-service line and leave the calling
telephone off the hook. This creates a busy signal on the line to all incoming communicators.
The communicators automatically switch to an unused line. The telephone company provides
rotary service when ordered.
i
Notice!
UL and Factory Mutual central station service standards require constant monitoring of tele-
phone lines.
Proper Ground
Connect the receivers to an earth ground, not a chassis or electrical ground. Measure the
resistance of the receiver ground to another ground. If the meter reads above 2Ω, check your
receiver ground against a third ground. If the difference is still greater than 2Ω, ground your