3. Guidelines for installation and electrical connections
3.2. Mains connection - power section
3 x AC 230 V (+10%; -15%) or
3 x AC 220 V (+15%; -10%)
50 to 60 Hz
The mains voltage can generally be adapted by using an autotransformer
(also see Section 3.5: "Requirements of the power supply system").
The KDV 2.3 can be directly connected to 3 x AC 220 V - power systems.
Connection voltage
Frequency
Mains connection via
transformer
NC
NC control unit
drive
module
drive
module
drive
module
stranded cable
diameter per EN 60 204 (VDE 0113)
1
2
L1
L2
L3
PE
3 x AC 50...60 Hz
16mm
2
1
2
NAKDV2.3
supply
module
PE-busbar in the
control cabinet
a
b
+
K1
16mm
2
16mm
2
16mm
2
Figure 3.2: Connecting the KDV 2.3 to the mains via an autotransformer
Each drive module must be connected to the PE busbar of the KDV
2.3 by a separate ground conductor.