D9412GV2/D7412GV2 | Operation and Installation Guide | 4.0 Installation
.
Bosch Security Systems, Inc. | 5/05 | F01U003641B 17
4.5.3 Enabling Ground Fault Detection
To configure the D9412GV2 and D7412GV2 Control
Panels to enable ground fault detection:
1. Set the silent relay in Area 5 to any value from 1
to 128. Do not use a zero (0) value.
The default value for the Area 5 silent relay
is 0 (zero). The 0 value disables the ground
fault detection function.
2. Close Switch S4 (Figure 3 on page 16). Refer to
Table 5 for information about the conditions for
enabling and disabling the Ground Fault
Detection Circuit.
Table 5: Ground Fault Detection Status
Ground Fault
Detection Circuit Switch S4
Value of Area 5
Silent Relay Alarm
Enabled Closed 1 to 128
Closed 0
Disabled
Open 0 to 128
4.5.4 D9412GV2 and D7412GV2 Ground Fault
Specifications
Table 6 provides the impedance specifications for
detecting ground faults when any terminal or field
wiring is shorted to ground.
Table 6: Ground Fault Impedance
Specifications
Impedance Control Panel Detects Ground Fault
300
Yes
300 to
200 k
No
200 k
Detection depends upon the terminal
4.5.5 Locking the Reset Pin
Locking the reset pin disables the control panel
(Figure 4). When the control panel is disabled, the
system ignores the keypads and points. CALL FOR
SERVICE appears in keypad displays when the pin is
locked down.
On-board relays (Terminals 6 and 7) and off-board
relays deactivate when the control panel is reset.
Terminal 8 has power when the relay is deactivated.
Activation interrupts power at that terminal. The on-
board relay (Terminal 8) remains deactivated when the
reset pin is locked in the disable position.
Releasing the reset pin from the closed position resets
the control panel. The control panel resets all its timers,
counters, indexes, and buffers. Any points that restore
after a reset do not generate Restoral Reports.
If the reset pin is placed in the disable position when
all areas are armed, there must be an entry in the
Answer Armed program item. Refer to RPS Parameters
in the D9412GV2/D7412GV2 Program Entry Guide
(P/N: F01U003636).
Locking the pin in the disable position applies power to
the control panel and charges the battery while the
detection devices and keypads are installed.
Figure 4: Reset Pin
Reset Pin
Disable All Except Battery
Charging And Programming
PERIPHERAL DEVICE CONNECTIONS
RED POWER +
YELLOW DATA BUS A
GREEN DATA BUS B
BLACK COMMON
32
31
30
29
1
2
1 - Reset pin locked (closed).
2 - Reset pin normal (open).