D9412GV2/D7412GV2 | Operation and Installation Guide | 6.0 Power Outputs
26 Bosch Security Systems, Inc. | 5/05 | F01U003641B
6.4.2 Terminals 6 and 7
When activated, Terminals 6 (Relay A) and 7 (Relay
B), provide positive (+) 10.2 VDC to 13.9 VDC power
output. Use the power at Terminals 6 and 7 to power
bells, siren drivers, piezoelectric fire sounders,
electronic horns, or other devices.
Programming determines the format of the output and
the conditions that activate it. One PTC protects
Terminals 6, 7, and 8 against shorts.
Available Power
The system combines the 1.4 A of primary power
produced by the power supply with the secondary
power source (the battery) to produce a total of 2.0 A
of alarm power at 10.2 VDC to 13.9 VDC. Terminals 6
and 7 share the available alarm power.
Power Restricted for Fire and Combined Fire and
Burglary Systems: Fire systems are prohibited from
using the battery for determining alarm power. Use the
fire system power formula that follows to calculate the
current available for fire and combined fire and
burglary systems.
6.4.3 Fire System Power Formula
To calculate the current available at Terminals 6 and 7
for fire and combined fire and burglary systems:
1. Add together the current draws for all devices
connected to Terminals 3, 8, 24, and 32, and the
accessory connector. This is the total current
required for the normal standby condition (NSC).
2. The current available for NSC is 1.4 A. Subtract
the NSC current required calculated in Step 1 from
the NSC current available, 1.4 A. The difference is
the alarm current available for Terminals 6 and 7.
In formula format:
1.4 A NSC current required
(Step 1)
=
Alarm current
available
Refer to the D9412GV2/D7412GV2 Approved
Applications Compliance Guide (P/N: F01U003639) for
module or accessory current requirements.
6.4.4 Terminal 8
Terminal 8 provides continuous positive (+) 10.2 VDC
to 13.9 VDC power. Relay C interrupts the power at
Terminal 8 when activated. Use Terminal 8 to power
smoke detectors or other devices that are reset by
interrupting power. One self-resetting circuit breaker
protects Terminals 6, 7, and 8 against shorts.
Verification/Reset Relay
The default program sets Relay C (Terminal 8) as a
verification and reset relay. Refer to Relay Parameters
and Point Assignments in the D9412GV2/D7412GV2
Program Entry Guide (P/N: F01U003636) for instructions
on programming verification and reset relays and
points.
Performing a sensor reset at a keypad produces a five-
second relay activation of verification/reset relays. The
control panel ignores verification/reset points during
the five seconds.