58 Bosch Security Systems, Inc. | 5/05 | F01U003641B
12.4.1 Access
Using Wiegand style cards or tokens, the D9210B can
allow access for up to 996 cards or tokens on the
D9412GV2, and up to 396 on the D7412GV2. User
access authority can be configured to restrict access to
certain doors or to certain periods of time. The reading
of access cards, in addition to granting access, can
control whether the system disarms. Used with the
D9412GV2, the D9210B recognizes 249 master users
by user name, passcode, and access authority. The
D9210B recognizes 99 master users when used with the
D7412GV2. Each master user supports three sub-users
with unique cards or tokens having the same access
level as the master user.
12.4.2 Switch Settings
Switches on the D9210B assign a unique address (1 to
8) to each module. Table 24 shows the correct switch
setting for each D9210B address.
Table 24: Address Switch Settings for
Access Control Module
DIP Switch Settings Door Module
Addresses
1 2 3 4
1
5
2
6
2
1 ON ON ON ON ON
2 OFF ON ON ON ON
---------------D7412GV2 Maximum---------------
3 ON OFF ON ON ON
4 OFF OFF ON ON ON
5 ON ON OFF ON ON
6 OFF ON OFF ON ON
7 ON OFF OFF ON ON
8 OFF OFF OFF ON ON
1
Switch 4, Fail Safe Mode:
ON = If SDI bus fails, relay energizes.
OFF = If SDI bus fails, relay de-energizes.
2
Switches 5 and 6 must remain in the ON position.
12.5 SDI Address 80
SDI Address 80, available on the D9412GV2 and
D7412GV2 Control Panels, allows for two-way SDI to
RS-232 information. This address is used with home or
building automation software. A D9133 Serial Interface
Module is required for this application.
12.5.1 Serial Interface Modules (SIMs)
The DX4010i RS-232 Serial Interface Module and the
D9133 Serial Interface Module are four-wire powered
SDI devices that provide connection for RS-232
devices to the D9412GV2 and D7412GV2 Control
Panels. They use a specific communication protocol
that is provided upon request. Contact Bosch Security
Systems Technical Support Monday through Friday
from 5 AM to 5 PM EST at 888-886-6189.
The DX4010i can be installed up to 305 m (1000 ft.)
from the control panel, using 0.8 mm (22 AWG) wire.
The DX4010i was not investigated by UL. Do not use
DX4010i in UL Listed installations.
The D9133 can be installed up to 305 m (1000 ft.) from
the control panel using 1.2 mm (18 AWG) wire. The
D9133 was not investigated by UL. Do not use D9133
in UL Listed installations.
12.5.2 Address Settings
No jumper settings are required for the D9133 (SDI
Address 80) for home or building automation purposes
(Figure 26). Remove the jumper shunts for this purpose.
Figure 26: D9133 Jumper Setting for Address 80
1234
80
The DX4010i has specific DIP switch settings for SDI
Address 80 when home or building automation is
desired. Figure 27 on page 59 shows the correct settings
for Address 80.
Page view 57