D9412GV2/D7412GV2 | Operation and Installation Guide | Specifications
72 Bosch Security Systems, Inc. | 5/05 | F01U003641B
Specifications
Table 27: Specifications
Primary: Terminals 1
and 2
16.5 VAC 40 VA class 2 plug-in transformer (D1640) Voltage Input
(Power Supply)
Secondary: Terminals 4
and 5
Sealed lead-acid rechargeable battery (12 VDC, 7 Ah or 12 VDC, 17.2 or 18 Ah).
The control panel supports up to two 12 VDC, 7 Ah batteries using the D122 Dual
Battery Harness or two D1218 (12 VDC, 17.2 or 18 Ah) batteries using a D122.
Current
Requirements
Control Panel: Idle 200mA; Alarm 500 mA
Refer to the Current Rating Chart for Standby Battery Calculations section in the D9412GV2/D7412GV2 Approved
Applications Compliance Guide (P/N: F01U003639) for the current draw requirements of other system components.
All external connections are power-limited except battery terminals.
Continuous
Power Outputs
Terminals 3,
24, and 32
1.4 A maximum at 10.2 VDC to 13.9 VDC (continuous supply) total for all devices
and outputs supplied at Terminals 3, 24, and 32 and at the accessory and
programming connectors.
Alarm Power
Output
Terminals 6
and 7
2.0 A maximum at 10.2 VDC to 13.9 VDC output. Output can be steady or one of
three pulsed patterns depending on programming. Refer to Relays in the
D9412GV2/D7412GV2 Program Entry Guide (P/N: F01U003636).
Switched Aux
Power
Terminal 8 1.4 A maximum at 10.2 VDC to 13.9 VDC output. Continuous output is interrupted
by Sensor Reset or alarm verification depending on programming. Refer to Relays in
the D9412GV2/D7412GV2 Program Entry Guide (P/N: F01U003636).
Power
Outputs*
Fire and
Fire/Burglary
Systems
To comply with UL 985 and 864 listing standards for fire alarm systems (effective March 1, 1989), the
total combined continuous and alarm current draw for the system during alarm conditions must be
limited to 1.4 A provided by the primary power supply (rectified AC). If current draw for the system
exceeds 1.4 A, remove connected devices until the current draw falls below 1.4 A. Then, connect the
removed devices to a D8132 Battery Charger Module or to an external power supply (refer to
Figure 25 on page 55).
Minimum
Operating
Voltage
10.2 VDC
SDI Bus SDI Bus A (+):
SDI Bus B (-):
9 VDC 4572 m (15000 ft) maximum
9 VDC 4572 m (15000 ft) maximum
Telephone
Connections
Connection:
Two telco
line
s:
RJ31X or RJ38X jack can connect the control panels.
Bosch Security Systems D928 Dual Phone Line Module required for two phone line service.
Supervision supplied by the control panel.
Discharge
Cycle
13.9 VDC
13.8 VDC
12.1 VDC
10.2 VDC
10.0 VDC
Charging float level.
Charging status LED on.
Low Battery and AC Fail Reports if programmed. Low Battery LED on.
Minimum operational voltage
Battery load shed (processing functions continue if AC is present).
Battery
Discharge/
Recharge
Schedule
Recharge
Cycle
AC ON
13.7 VDC
13.9 VDC
Load shed relay resets, battery charging begins, Battery Trouble and AC Restoral
Reports sent.
Battery Restoral Report sent, Low Battery LED off.
Charging status LED off, battery float charged.
Temperature: 0°C to +50°C (+32°F to +122°F) Environmental
Relative
Humidity:
Maximum 95% non-condensing
Arming
Stations
D720 Command Center, D1255 Command Center, D1256 Fire Command Center; D1257 Fire Alarm Annunciator;
D1260 Alpha V Command Center; Keyswitch
Point
Thresholds
On-board Points
1 to 8
Open
Normal
Short
Greater than 3.7 VDC, but less than 5.0 VDC.
Greater than 2.0 VDC, but less than 3.0 VDC.
Greater than 0.0 VDC, but less than 1.3 VDC.
Compatible
Enclosures
D8103 Universal Enclosure, D8109 Fire Enclosure, D8108A Attack Resistant Enclosure, BATB-40 Battery Box