Bosch D9412GV2 User Manual Page 64

  • Download
  • Add to my manuals
  • Print
  • Page
    / 74
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 63
D9412GV2/D7412GV2 | Operation and Installation Guide | Appendix A: System Wiring Diagrams, Issue A
64 Bosch Security Systems, Inc. | 5/05 | F01U003641B
Appendix A: System Wiring Diagrams, Issue A
A.1 D9412GV2 Control Panel
Figure 34: D9412GV2, Power Supply Side
D1640
16.5 V, 40 VA
60 Hz
Tra nsform er
+
AUX PWR
ALARM TRIG
COM
SUPV IN
ALARM CKT
D192C/D/G
-
D928
C900
D8132
Battery
Charger
D126
Battery
12 V, 7 Ah
or
D1218
12 V, 17.2 Ah
or 18.0 Ah
D126
Battery
12 V, 7 Ah
or
D1218
12 V, 17.2 Ah
or 18.0 Ah
D126
or
D1218
- +
D113
BAT 2+
BAT 1+
BAT 2-
BAT 1-
SUPV
CHGR+
CHGR-
VAUX+
-
+
D126
or
D1218
-
+
D126
or
D1218
-
+
D126
or
D1218
EARTH GROUND
COMMON
BATTERY NEGATIVE ONLY
Maximum Charging
Current 1.4 Amps.
BATTERY POSITIVE ONLY
RELAY A
RELAY B
RELAY C
+ AUX POWER
1
2
3
4
5
6
7
8
9
10
CLASS 2 TRANSFORM ER
16.5 VAC 40 VA 60 Hz
Model D 1640
Internally Fused - Do Not short
Requires Unswitched Outlet
Do Not Share With Other Equipment
PROGRAMMABLE
ALARM OUTPUTS
Te rmi na ls
Requires Optional
Model D136 Relay
In ALT ALARM
& SW AUX
&
78
GROUND FAULT DETECT
Enabled
Disabled
GRN
PROG
CONN
1211 13
Point 1 Point 2
1514 16
Point 3 Point 4
D9412GV2
PHONE
LED
RED
ON when
communicating
OFF when idle
PHONE LINE SEIZED
TIP
RING
TELCO
Point 8
S3 Option
Enabled:
Closed = 1K
EOL
Norm al O pe rat io n
Disabled:
Open =AB-12 UL
Bell Box 220 K
1 - If required by local AHJ, connect D113 Battery
Lead Supervision Module.
2 - D122 Dual Battery Harness, as required.
3 - D1640 Transformer and D8004 Transformer
Enclosure required for NFPA Applications
4 - D8132 Dual Battery Charger with two batteries
(batteries are not supervised)
5 - Power limited, supervised
6 - Power limited
7 - To Relay A or Relay B
8- Listed Audible Signaling Devices rated at 10.2
to 13.8 VDC (Do not use vibrating type horns.)
9- Optional
10- 560
, 2
EOL Resistor (P/N: 15-03130-005)
11- RJ31X, Secondary phone line
12- RJ31X, Jack
13- RJ31X, Primary phone line
14- To earth ground
Page view 63
1 2 ... 59 60 61 62 63 64 65 66 67 68 69 ... 73 74